OSHA Inspection: SUNBELT RENTALS

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of SUNBELT RENTALS in 2211 OAKLEAF STREET, JOLIET, IL 60436 (NAICS 532412). OSHA activity number 333892024.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Sunbelt Rentals for free Get an email when a new federal OSHA severe-injury report for Sunbelt Rentals is published. One employer, no account, unsubscribe in one click.
Establishment
SUNBELT RENTALS
Site address
2211 OAKLEAF STREET
City
JOLIET
State
IL
ZIP
60436
Mailing
2211 OAKLEAF STREET, JOLIET, IL 60436
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
532412
Employees
13
Ownership type
Private (A)

5 citations on file for this inspection.

1910.94 A04 I

Deleted Serious Gravity 5 1 instance 6 exposed
Issued
May 17, 2012
Abate by
Jun 8, 2012
Penalty
Initial $4,000 · Current $0 Reduced
29 CFR 1910.94(a)(4)(i): The construction, installation, inspection, or maintenance of exhaust system(s) did not conform to the principles or requirements set forth in American National Standards Institute Fundamentals Governing the Design and Operation of Local Exhaust Systems Z9.2 1960 and ANSI Z33.1 1961:      a) On or about April 18, 2012, at the above located workplace employees were required to work with and around a natural gas fired power washer that released exhaust gases into the building. The exhaust gas ventilation system did not meet the principles or requirements set forth in the American National Standards Institute Fundamentals Governing the Design and Operation of Local Exhaust Systems Z9.2 1960 and ANSI Z33.1 1961. Employees were thereby exposed to the hazards associated with exhaust gases including but not limited to carbon monoxide.
Recent events (2)
  • · I (S) $0
  • · Z (S) $4000

1910.303 B02

Other-than-serious 2 instances 4 exposed
Issued
May 17, 2012
Abate by
Jun 8, 2012
Penalty
Initial $4,000 · Current $4,000
29 CFR 1910.303(b)(2): Listed or labeled equipment was not used or installed in accordance with instructions included in the listing or labeling:    a) On or about April 18, 2012, at the above located workplace, employees in the in the shop were required to work with and around a Shark power washer.  The power washer was missing a cover and had exposed energized (120 volt) wiring. Employees were thereby exposed to hazards associated with 120 volts of electricity.    b) On or about April 18, 2012, at the above located workplace, employees in the in the shop were required to work with and around a on an Emglo air compressor. The air compressors electrical pressure cutoff switch was missing a cover and had exposed energized (240 volt) wiring. Employees were thereby exposed to hazards associated with 240 volts of electricity.
Recent events (2)
  • · I (O) $4000
  • · Z (S) $4000

1910.303 G02 I

Other-than-serious 1 instance 6 exposed
Issued
May 17, 2012
Abate by
Jun 8, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(2)(i):  Electrical equipment operating at 50 volts or more was not guarded against accidental contact by approved cabinets or other forms of approved enclosures:    a) On or about April 18, 2012, at the above located workplace, employees in the in the shop were required to work with and around a Shark power washer.  The power washer had exposed energized (120 volt) wiring that was not guarded by an approved cabinet or other approved enclosure. Employees were thereby exposed to hazards associated with 120 volts of electricity.    b) On or about April 18, 2012, at the above located workplace, employees in the in the shop were required to work with and around a on an Emglo air compressor. The air compressor had exposed energized (240 volt) wiring that was not guarded by an approved cabinet or other approved enclosure. Employees were thereby exposed to hazards associated with 240 volts of electricity.
Recent events (2)
  • · I (O) $0
  • · Z (S) $0

1904.32 B06

Other-than-serious 1 instance 10 exposed
Issued
May 17, 2012
Abate by
May 18, 2012
Penalty
Initial $0 · Current $0
29 CFR 1904.32(b)(6):  The Summary of Work-Related Injuries and Illnesses (OSHA Form 300A or equivalent) for the previous year was not posted between February 1 and April 30:    On or about April 18, 2012, at the above located workplace, the employer did not have a copy of the 2011 annual summary (OSHA 300A) posted in a conspicuous place.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.23 A08

Other-than-serious 1 instance 6 exposed
Issued
May 17, 2012
Abate by
Jun 8, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.23(a)(8): Every floor hole into which persons can accidentally walk were not guarded by either a standard railing or floor hole cover:    a) On or about April 18, 2012, at the above located workplace, employees were required to work around a floor hole measuring approximately 5 inches by 5 inches. Employees were thereby exposed to trips and falls hazards.