Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,198,201Inspections Most recent open 2026-08-31 Last loaded 2026-09-03

OSHA Inspection: EDSAL MFG, CO.

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of EDSAL MFG, CO. in 4400 S. PACKERS AVE, CHICAGO, IL 60609 (NAICS 337215). OSHA activity number 333926053.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Edsal MFG, CO. for free Get an email when a new federal OSHA severe-injury report for Edsal MFG, CO. is published. One employer, no account, unsubscribe in one click.
Establishment
EDSAL MFG, CO.
Site address
4400 S. PACKERS AVE
City
CHICAGO
State
IL
ZIP
60609
Mailing
4400 S. PACKERS AVE, CHICAGO, IL 60609
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
337215
Employees
1000
Ownership type
Private (A)

4 citations on file for this inspection.

1910.303 B02

Serious Gravity 5 2 instances 12 exposed
Issued
Jun 4, 2012
Abate by
Jun 25, 2012
Penalty
Initial $4,000 · Current $2,800 Reduced
29 CFR 1910.303(b)(2): Listed or labeled equipment was not used or installed in accordance with instructions included in the listing or labeling:    a) During the period of March 19, 2012 and April 19, 2012, at the above located workplace employees in the lunch room were allowed to use a 120 volt Quasar microwave that was missing a grounding pin.       b) During the period of March 19, 2012 and April 19, 2012, at the above located workplace employees in the lunch room were allowed to use a 120 volt Sharp commerical microwave that was missing a grounding pin.    c) During the period of March 19, 2012 and April 19, 2012, at the above located workplace employees at welding station 15 were required to work with and around a 240 volt disconnect box which was not approved to be used in wet or damp locations.    d) During the period of March 19, 2012 and April 19, 2012, at the above located workplace employees at welding station 28 were required to work with and around a 240 volt disconnect box which was not approved to be used in wet or damp locations.
Recent events (2)
  • · I (S) $2800
  • · Z (S) $4000

1910.305 E01

Serious Gravity 10 2 instances 12 exposed
Issued
Jun 4, 2012
Abate by
Jun 25, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed so as to prevent moisture or water from entering and accumulating within the enclosure.  In wet locations the enclosure was not weatherproof.    a) During the period of March 19, 2012 and April 19, 2012, at the above located workplace, employees at welding station 15, used a 240 volt disconnect box in a wet location the enclosure was not weatherproof.      b) During the period of March 19, 2012 and April 19, 2012, at the above located workplace, employees at welding station 28, used a 240 volt disconnect box in a wet location the enclosure was not weatherproof.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.334 A03 I

Serious Gravity 5 30 exposed
Issued
Jun 4, 2012
Abate by
Jun 25, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.334(a)(3)(i): A flexible cord used with grounding type equipment shall contain an equipment grounding conductor.    a) During the period of March 19, 2012 and April 19, 2012, at the above located workplace, employees used two mirowaves that were not equipped with the required grounding pins, the employees were thereby exposed to electrical hazards.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1904.32 B03

Other-than-serious 1 instance 50 exposed
Issued
Jun 4, 2012
Abate by
Jun 25, 2012
Penalty
Initial $0 · Current $0
29 CFR 1904.32(b)(3):  The Summary of Work-Related Injuries and Illnesses (OSHA Form 300A or equivalent) was not properly certified:    a) On or about April 19, 2012, at the above located workplace, the employers OSHA 300A summaries for 2011 was not properly certified by a company executive.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

View Edsal MFG, CO.'s full OSHA safety record →