OSHA Inspection: UEI ELECTRIC INC

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of UEI ELECTRIC INC in 4356 COMMERCE DRIVE, BATAVIA, NY 14020 (NAICS 238210). OSHA activity number 333938421.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch UEI Electric INC — free Get an email when a new federal OSHA severe-injury report for UEI Electric INC is published. One employer, no account, unsubscribe in one click.
Establishment
UEI ELECTRIC INC
Site address
4356 COMMERCE DRIVE
City
BATAVIA
State
NY
ZIP
14020
Mailing
1518 CLIFFORD DRIVE, ERIE, PA 16505
Inspection type
Unprogrammed Other (I)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
3
Ownership type
A

6 citations on file for this inspection.

1926.403 B02

Serious Gravity 1 1 instance 3 exposed
Issued
Jun 14, 2012
Penalty
Initial $1,200 · Current $300 Reduced
29 CFR 1926.403(b)(2):     Installation and use. Listed, labeled, or certified equipment shall be installed and used in accordance with instructions included in the listing, labeling, or certification.    a) On or about 4/19/12 at the Holiday Inn Express located at 4356 Commerce Drive, Batavia, New York; the temporary light strings were spliced together with 4"x4" boxes with prepunched knockouts. The boxes were not fastened as required by the listing and labeling of the equipment.    NO ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $300
  • — Z (S) $1200

1926.405 A02 II E

Serious Gravity 1 1 instance 3 exposed
Issued
Jun 14, 2012
Penalty
Initial $1,200 · Current $300 Reduced
29 CFR 1926.405(a)(2)(ii)(E):     Lamps used in temporary wiring for general illumination were not protected from accidental contact or breakage:    a) On or about 4/19/12 at the Holiday Inn Express located at 4356 Commerce Drive, Batavia, New York; the temporary light strings on all four floors and stairways were missing protective baskets for the lamps.    NO ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $300
  • — Z (S) $1200

1926.405 B01

Serious Gravity 1 1 instance 3 exposed
Issued
Jun 14, 2012
Penalty
Initial $1,200 · Current $300 Reduced
29 CFR 1926.405(b)(1):     Conductors entering boxes, cabinets, and fittings were not protected from abrasion:    a) On or about 4/19/12 at the Holiday Inn Express located at 4356 Commerce Drive, Batavia, New York; temorary light strings were spliced together using a 4"x4" box. The cable clamps for the box were attached directly to the conductors.    NO ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $300
  • — Z (S) $1200

1926.405 B02

Serious Gravity 1 1 instance 3 exposed
Issued
Jun 14, 2012
Penalty
Initial $1,200 · Current $300 Reduced
29 CFR 1926.405(b)(2):     All pull boxes, junction boxes, and fittings were not provided with covers:    a) On or about 4/19/12 at the Holiday Inn Express located at 4356 Commerce Drive, Batavia, New York; a 4"x4" box used to splice light strings together did not have a cover.    NO ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $300
  • — Z (S) $1200

1926.405 J01 I

Serious Gravity 1 1 instance 3 exposed
Issued
Jun 14, 2012
Penalty
Initial $1,200 · Current $300 Reduced
29 CFR 1926.405(j)(1)(i):     Fixtures, lampholders, lamps, rosettes, or receptacles had live parts normally exposed to employee contact:    a) On or about 4/19/12 the Holiday Inn Express located at 4356 Commerce Drive, Batavia, New York; on all four floors the were lamps missing from the energized sockets of the temporary lighting.    NO ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $300
  • — Z (S) $1200

1926.1052 C01 I

Serious Gravity 5 1 instance 3 exposed
Issued
Jun 14, 2012
Penalty
Initial $1,600 · Current $500 Reduced
29 CFR 1926.1052(c)(1)(i):     Stairways having four or more risers or rising more than 30 inches (76 cm), whichever is less, were not equipped with at least one handrail:    a) On or about 4/19/12 at the new Holiday Inn Express located at 4356 Commerce Drive, Batavia, New York; employees working in a 4 story building were using the stairways at each end of the building to access work areas on the upper floors. Neither stairway was equipped with handrails.    NO ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $500
  • — Z (S) $1600