BRONX, NY ·
OSHA Inspection: RUBIN BROS. PRODUCE CORP.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of RUBIN BROS. PRODUCE CORP. in 147 NYC TERMINAL MARKET, BRONX, NY 10474 (NAICS 424910). OSHA activity number 334152865.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- RUBIN BROS. PRODUCE CORP.
- Site address
- 147 NYC TERMINAL MARKET
- City
- BRONX
- State
- NY
- ZIP
- 10474
- Mailing
- 147 NYC TERMINAL MARKET, BRONX, NY 10474
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 424910
- Employees
- 60
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.178 P01
- Issued
- Oct 30, 2012
- Penalty
- Initial $2,142 · Current $1,607 Reduced
General-duty citation text
29 CFR 1910.178(p)(1): If at any time a powered industrial truck is found to be in need of repair, defective, or in any way unsafe, the truck shall be taken out of service until it has been restored to safe operating condition. a) Job Site, Building 269, Row B: A "Crown" HI-LO industrial trucks. Serial number 1A343042, Model RC5520/30, Serial number 1A343045. Model Number, RC5520-30 and Serial number 1A343044, Model RC5520-30. The back up alarms were broken on these three Hi-LO's; on or about 5/3/2012.
Recent events (2)
- · I (S) $1606.5
- · Z (S) $2142
1910.303 F01
- Issued
- Oct 30, 2012
- Penalty
- Initial $2,142 · Current $1,607 Reduced
General-duty citation text
29 CFR 1910.303(f)(1): Each disconnecting means required by this subpart for motors and appliances shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident. a) Job Site, Row B, #269, Back Platform: The three (3) electrical service panels were not marked as to thier purpose: on or about 5/3/2012.
Recent events (2)
- · I (S) $1606.5
- · Z (S) $2142
1910.304 F01 IV
- Issued
- Oct 30, 2012
- Penalty
- Initial $2,678 · Current $2,009 Reduced
General-duty citation text
29 CFR 1910.304(f)(1)(iv): Overcurrent devices shall be readily accessible to each employee or authorized building management personnel. These overcurrent devices may not be located where they will be exposed to physical damage or in the vicinity of easily ignitable material. a) Job Site, Building 269, Row B: Three electrical panels were obstructed with paper cartoons, pallets; on or about 5/3/12.
Recent events (2)
- · I (S) $2008.5
- · Z (S) $2678
1910.305 B01
- Issued
- Oct 30, 2012
- Penalty
- Initial $2,142 · Current $1,607 Reduced
General-duty citation text
29 CFR 1910.305(b)(1): Conductors entering boxes, cabinets, or fittings were not effectively closed. a) Row B, Building 269, Back Platform: The unused breaker openings in the electrical service panel were not provided with filler blocks or otherwise guarded to protect an employee from accidentally contacting the energized electrical equipment contained within the panel: on or about 5/3/12.
Recent events (2)
- · I (S) $1606.5
- · Z (S) $2142
More inspections in this industry (NAICS 424910)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 334152865.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.