BRONX, NY ·
OSHA Inspection: M & R TOMATO DISTRIBUTORS, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of M & R TOMATO DISTRIBUTORS, INC. in 151 NYC TERMINAL MARKET, BRONX, NY 10474 (NAICS 424910). OSHA activity number 334191244.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- M & R TOMATO DISTRIBUTORS, INC.
- Site address
- 151 NYC TERMINAL MARKET
- City
- BRONX
- State
- NY
- ZIP
- 10474
- Mailing
- 151 NYC TERMINAL MARKET, BRONX, NY 10474
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 424910
- Employees
- 13
- Ownership type
- Private (A)
Citations
3 citations on file for this inspection.
1910.303 G02 I
- Issued
- Oct 30, 2012
- Penalty
- Initial $1,020 · Current $510 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by this standard, live parts of electric equipment operating at 50 volts or more shall be guarded against accidentalcontact by use of approved cabinets or other forms of approved enclosures or by any of the following means: A) Job Site, North Wall, Packing Department: The switch outlet box was not provided with a cover, on or about 5/3/2012.
Recent events (2)
- · I (S) $510
- · Z (S) $1020
1910.304 G05
- Issued
- Oct 30, 2012
- Penalty
- Initial $1,360 · Current $680 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): Grounding path. The path to ground from circuits, equipment, and enclosures shall be permanent, continuous, and effective. a) Job Site, East Wall, Main Store: A Yale jack pallet, serial number A824N07621 was connected to an outlet that was not grounded: on or about 5/3/2012. b) Job Site, East Wall, Main Store: An extension cord connected from the Yale Pallet jack to the wall outlet had the ground pin broken off: on or about 5/3/12.
Recent events (2)
- · I (S) $680
- · Z (S) $1360
1910.305 B01
- Issued
- Oct 30, 2012
- Penalty
- Initial $1,360 · Current $680 Reduced
General-duty citation text
29 CFR 1910.305(b)(1): Conductors entering boxes, cabinets, or fittings were not effectively closed: A) Job Site, North Wall, Packing Department, Middle Panel: The unused circuit breaker openings in the electrical panel were not provided with filler blocks or otherwise guarded to protect an employee from accidentally contacting the energized electrical equipment contained within the panel, on or about 5/3/12.
Recent events (2)
- · I (S) $680
- · Z (S) $1360
More inspections in this industry (NAICS 424910)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 334191244.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.