Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,197,124Inspections Most recent open 2026-08-25 Last loaded 2026-08-28

OSHA Inspection: M & R TOMATO DISTRIBUTORS, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of M & R TOMATO DISTRIBUTORS, INC. in 151 NYC TERMINAL MARKET, BRONX, NY 10474 (NAICS 424910). OSHA activity number 334191244.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch M & R Tomato Distributors, INC. for free Get an email when a new federal OSHA severe-injury report for M & R Tomato Distributors, INC. is published. One employer, no account, unsubscribe in one click.
Site address
151 NYC TERMINAL MARKET
City
BRONX
State
NY
ZIP
10474
Mailing
151 NYC TERMINAL MARKET, BRONX, NY 10474
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424910
Employees
13
Ownership type
Private (A)

3 citations on file for this inspection.

1910.303 G02 I

Serious Gravity 1 1 instance 4 exposed
Issued
Oct 30, 2012
Penalty
Initial $1,020 · Current $510 Reduced
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by this standard, live parts of electric equipment operating at 50 volts or more shall be guarded against accidentalcontact by use of approved cabinets or other forms of approved enclosures or by any of the following means:    A) Job Site, North Wall, Packing Department:  The switch outlet box was not provided with a cover, on or about 5/3/2012.
Recent events (2)
  • · I (S) $510
  • · Z (S) $1020

1910.304 G05

Serious Gravity 5 2 instances 1 exposed
Issued
Oct 30, 2012
Penalty
Initial $1,360 · Current $680 Reduced
29 CFR 1910.304(g)(5): Grounding path. The path to ground from circuits, equipment, and enclosures shall be permanent, continuous, and effective.    a) Job Site, East Wall, Main Store:  A Yale jack pallet, serial number A824N07621 was connected to an outlet that was not grounded: on or about 5/3/2012.     b) Job Site, East Wall, Main Store: An extension cord connected from the Yale Pallet jack to the wall outlet had the ground pin broken off: on or about 5/3/12.
Recent events (2)
  • · I (S) $680
  • · Z (S) $1360

1910.305 B01

Serious Gravity 5 1 instance 4 exposed
Issued
Oct 30, 2012
Penalty
Initial $1,360 · Current $680 Reduced
29 CFR 1910.305(b)(1): Conductors entering boxes, cabinets, or fittings were not effectively closed:     A) Job Site, North Wall, Packing Department, Middle Panel: The unused circuit breaker openings in the electrical panel were not provided with filler blocks or otherwise guarded to protect an employee from accidentally contacting the energized electrical equipment contained within the panel, on or about 5/3/12.
Recent events (2)
  • · I (S) $680
  • · Z (S) $1360

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 334191244.