CHARLESTON, WV ·
OSHA Inspection: BENI KEDEM SHRINE CENTER
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of BENI KEDEM SHRINE CENTER in 100 QUARRIER STREET, CHARLESTON, WV 25301 (NAICS 813410). OSHA activity number 334252145.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BENI KEDEM SHRINE CENTER
- Site address
- 100 QUARRIER STREET
- City
- CHARLESTON
- State
- WV
- ZIP
- 25301
- Mailing
- 100 QUARRIER STREET, CHARLESTON, WV 25301
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 813410
- Employees
- 5
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.106 E07 I A
- Issued
- Jul 12, 2012
- Abate by
- Jul 13, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.106(e)(7)(i)(a): All electrical wiring and equipment was not installed according to the requirements of Subpart S of this part: (a) Boiler Room: An employee accesses the boiler room to fill weed eaters with gasoline. There are 25 gallons of catagory three flammable liquids. An active electrical outlet was found 19 inches from the the flammable liquids. The electrical outlet used in a Class 1, Division 2 location was not intrinsically safe, approved for Class 1, Division 2 location, or safe for a Class 1, Division 2 location, as observed on or about 05/11/2012. ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
- · Z (S) $0
1910.157 E02
- Issued
- Jul 12, 2012
- Abate by
- Jul 13, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly: (a) Boiler Room: The employer failed to visually inspect all portable fire extinguishers in the facility on a monthly basis as determined on or about 05/11/2012. ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
- · Z (S) $0
1910.157 E03
- Issued
- Jul 12, 2012
- Abate by
- Jul 13, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check: (a) Boiler Room: Portable fire extinguishers located throughout the facility had not been subjected to an annual maintenance check as determined on or about 05/11/2012. ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
- · Z (S) $0
1910.157 G01
- Issued
- Jul 12, 2012
- Abate by
- Jul 13, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(g)(1): An educational program was not provided for all employees to familiarize them with the general principles of fire extinguisher use and the hazards involved with incipient stage fire fighting: (a) Facility Wide: The employer provides fire extinguishers in the facility, but does not require the employees to put out incipeint stage fires. The employer failed to provide training on the general principles of fire extinguisher use to the employees, as determined on or about 05/11/2012. ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
- · Z (S) $0
1910.305 B02
- Issued
- Jul 12, 2012
- Abate by
- Jul 13, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: (a) Boiler Room: An employee accesses the boiler room to fill weed eaters with gasoline. There are 25 gallons of catagory three flammable liquids. An active electrical outlet was found 19 inches from the the flammable liquids. The electrical outlet box's faceplate did not cover the outlet opening exposing the internal wiring to flammable vapor, as observed on or about 05/11/2012. ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
- · Z (S) $0
1910.1200 E01
- Issued
- Jul 12, 2012
- Abate by
- Jul 13, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(e)(1): The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) will be met: (a) Beni Kedem Shrine Center: The employer had not developed a written chemical hazard communication program for employees who use hazardous chemicals including, but not limited to, Gasoline, which contains Benzene, as determined on or about 05/11/2012. ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
- · Z (S) $0
1910.1200 G08
- Issued
- Jul 12, 2012
- Abate by
- Jul 13, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(g)(8): The employer did not maintain copies of the required material safety data sheets for each hazardous chemical in the workplace: (a) Facility Wide: Employees use chemicals such as but not limited to Gasoline, which contains Benzene, to conduct maintenance work. The employer did not maintain copies of the required material safety data sheet, as determined on or about 05/11/2012. ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
- · Z (S) $0
1910.1200 H03
- Issued
- Jul 12, 2012
- Abate by
- Jul 13, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(h)(3): The employee training did not include the requirements of 29 CFR 1910.1200(h)(3)(i) through (h)(3)(iv): (a) Beni Kedem Shrine Center: The employees were not provided training on the hazards associated with their use including, but not limited to, Gasoline, which contains Benzene, as determined on or about 05/11/2012. ABATEMENT CERTIFICATION REQUIRED