Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,191,871Inspections Most recent open 2026-07-30 Last loaded 2026-08-03

OSHA Inspection: ENTERPRISE EAGLE TERMINAL

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of ENTERPRISE EAGLE TERMINAL in 520 MILFORD ROAD, UWCHLAND, PA 19480 (NAICS 488999). OSHA activity number 334314929.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Enterprise Eagle Terminal for free Get an email when a new federal OSHA severe-injury report for Enterprise Eagle Terminal is published. One employer, no account, unsubscribe in one click.
Site address
520 MILFORD ROAD
City
UWCHLAND
State
PA
ZIP
19480
Mailing
1100 LOUISIANA STREET, HOUSTON, TX 77002
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
488999
Employees
5
Ownership type
A

4 citations on file for this inspection.

1910.38 C02

Deleted Serious Gravity 5 1 instance 4 exposed
Issued
Sep 5, 2012
Abate by
Sep 26, 2012
Penalty
Initial $5,000 · Current $0 Reduced
29 CFR 1910.38(c)(2):     Procedures for emergency evacuation, including type of evacuation and exit route assignments;    a) Jobsite - Brick perimeter security wall, west side, Eagle Terminal - The Enterprise Emergency Response Plan did not include three emergency exit routes (emergency escape ladders) installed on the west brick perimeter security wall.  Observed on or about 4/30/2012.    Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (3)
  • · C (S) $5000
  • · F (S) $0
  • · Z (S) $5000

1910.37 A03

Other-than-serious 1 instance 4 exposed
Issued
Sep 5, 2012
Abate by
Sep 26, 2012
Penalty
Initial $0 · Current $2,500
29 CFR 1910.37(a)(3):     Exit routes were not free and/or unobstructed. No materials or equipment may be placed, either permanently or temporarily, within the exit route. The exit access must not go through a room that can be locked, such as a bathroom, to reach an exit or exit discharge, nor may it lead into a dead-end corridor. Stairs or a ramp were not provided where the exit route was not substantially level.    Three emergency exit routes using folding escape ladders with metal rungs and fabric rails over the interior side of an eight foot brick perimeter security fence were not free and/or unobstructed.  The folding ladders were emergency exit routes for workers who may be isolated between the brick security fence and a catastrophic event, such as with the eighteen 30,000 gallon LPG tanks.   There also was no means provided for descending the eight foot wall on the exterior side.      Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (3)
  • · C (S) $0
  • · F (O) $2500
  • · Z (S) $0

1910.119 D03 I

Other-than-serious 1 instance 4 exposed
Issued
Sep 5, 2012
Abate by
Sep 26, 2012
Penalty
Initial $5,000 · Current $2,500 Reduced
29 CFR 1910.119(d)(3)(i):     The employer did not compile information pertaining to the equipment in the process:    The process safety information documentation, "Eagle Terminal Process Information", did not list Bank C LPG tanks, incorrectly listed number, make and model PSVs for the LPG tanks, incorrectly listed the PSV code certifying agency, and incorrectly listed the PSV design specifics/sizing.      Abatement certification and documentation required within 10 days after abatement date. The certification shall include a statement that abatement is complete, the date and method of abatement, and state that employees and their representatives were informed of this abatement. Abatement documentation shall include documents demonstrating that abatement is complete, such as evidence of the purchase or repair of equipment, photographic or video evidence of abatement or other written records.
Recent events (3)
  • · C (S) $5000
  • · F (O) $2500
  • · Z (S) $5000

1910.119 J04 II

Deleted Serious Gravity 10 1 instance 4 exposed
Issued
Sep 5, 2012
Abate by
Sep 26, 2012
Penalty
Initial $5,000 · Current $0 Reduced
29 CFR 1910.119(j)(4)(ii): Inspection and testing procedures did not follow recognized and generally accepted good engineering practices.     a) Jobsite: Eagle Terminal, 520 Milford Road, Uwchland, PA 19480 - Testing, setting and cleaning of pressure relief devices for the LPG storage tanks did not follow recognized and generally accepted good engineering practices including but not limited to the State of Pennsylvania Code for Unfired Pressure Vessels, REGO (pressure relief device manufacturer) Pressure Pressure Relief Valve Repair and Testing, UL- 132 Safety Relief Valves for Anhydrous Ammonia and LP-Gas, CGA S-1.3 Pressure Relief Device Standards, and Enterprise Products Inspection and Testing of Pressure Relief Devices Standard, STD 9501.    Abatement certification and documentation required within 10 days after abatement date. The certification shall include a statement that abatement is complete, the date and method of abatement, and state that employees and their representatives were informed of this abatement. Abatement documentation shall include documents demonstrating that abatement is complete, such as evidence of the purchase or repair of equipment, photographic or video evidence of abatement or other written records.
Recent events (3)
  • · C (S) $5000
  • · F (S) $0
  • · Z (S) $5000

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 334314929.