Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,197,549Inspections Most recent open 2026-08-27 Last loaded 2026-08-31

OSHA Inspection: CARIBOU NURSING HOME, INC.

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of CARIBOU NURSING HOME, INC. in 162 ACADEMY STREET, PRESQUE ISLE, ME 04769 (NAICS 623110). OSHA activity number 334337912.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Caribou Nursing Home, INC. for free Get an email when a new federal OSHA severe-injury report for Caribou Nursing Home, INC. is published. One employer, no account, unsubscribe in one click.
Site address
162 ACADEMY STREET
City
PRESQUE ISLE
State
ME
ZIP
04769
Mailing
162 ACADEMY STREET, PRESQUE ISLE, ME 04769
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
623110
Employees
133
Ownership type
Private (A)

2 citations on file for this inspection.

1910.303 B07 I

Other-than-serious 1 instance 4 exposed
Issued
Jun 21, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(7)(i):     Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings shall be effectively closed to afford protection substantially equivalent to the wall of the equipment.    Electrical Room - The receptacle box with energized wires enclosed did not have a cover plate.
Recent events (1)
  • · Z (O) $0

1910.303 G01 I A

Other-than-serious 1 instance 4 exposed
Issued
Jun 21, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(i)(A):     For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening whwere they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910:  (a) (LOCATION) (IDENTIFY EQUIPMENT AND CONDITION(S)) (STATE HAZARD(S) TO EMPLOYEE(S) AND SPECIFY DISTANCE REQUIRED)      Electrical Room -  The breaker sub-panel did not have 36" working space clear in front of the panel. Some construction materials had been stored in front of the panel.
Recent events (1)