OSHA Inspection: RIO GRANDE COMMODITIES

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of RIO GRANDE COMMODITIES in 2485 EAST ROAD 4 NORTH, MONTE VISTA, CO 81144 (NAICS 424510). OSHA activity number 334354313.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch RIO Grande Commodities for free Get an email when a new federal OSHA severe-injury report for RIO Grande Commodities is published. One employer, no account, unsubscribe in one click.
Site address
2485 EAST ROAD 4 NORTH
City
MONTE VISTA
State
CO
ZIP
81144
Mailing
2485 EAST ROAD 4 NORTH, MONTE VISTA, CO 81144
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424510
Employees
7
Ownership type
A

7 citations on file for this inspection.

1910.27 D02

Serious Gravity 5 5 instances 3 exposed
Issued
Jun 22, 2012
Abate by
Aug 6, 2012
Penalty
Initial $1,700 · Current $850 Reduced
29 CFR 1910.27(d)(2): When ladders are used to ascend to heights exceeding 20 feet there were no cage, well, or ladder safety devices provided:    a) On or about May 8, 2012 and times prior, employees were exposed to injuries for falls to the lower surface at the following locations, bins 4, 5, A, B, and C. The bins had ladders installed to gain access to their top hatches at heights greater than 20 feet and there were no cages installed.    Abatement Note: Abatement certification is required for this item (see enclosed "Certification of Corrective Action Worksheet").
Recent events (2)
  • · I (S) $850
  • · Z (S) $1700

1910.27 C04

Serious Gravity 5 12 instances 3 exposed
Issued
Jun 22, 2012
Abate by
Aug 6, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.27(c)(4): The distance from the centerline of rungs, cleats, or steps to the nearest permanent object in back of the ladder was less than 7 inches, except that when unavoidable obstructions are encountered, minimum clearances as shown in figure D-3 shall be provided:    a) On or about May 8, 2012, and times prior, employees were exposed to injuries for falls to the lower surface at the following locations, bins 1,2,3,8,9,11 - 17. The distance from the centerline of the rungs to the bin was less than 7 inches on all the access ladders of these bins.    Abatement Note: Abatement certification is required for this item (see enclosed "Certification of Corrective Action Worksheet").
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.333 A02

Serious Gravity 5 1 instance 3 exposed
Issued
Jun 22, 2012
Abate by
Jun 25, 2012
Penalty
Initial $1,700 · Current $850 Reduced
29 CFR 1910.333(a)(2): If the exposed live parts are not deenergized (i.e., for reasons of increased or additional hazards or infeasibility), other safety-related work practices were not used to protect employees who may be exposed to the electrical hazards involved. Such work practices did not protect employees against contact with energized circuit parts directly with any part of their body or indirectly through some other conductive object. The work practices that are used were not suitable for the conditions under which the work is to be performed and for the voltage level of the exposed electric conductors or circuit parts. Specific work practice requirements are detailed in paragraph (c) of this section:    a) On or about May 8, 2012 and times prior, employees were exposed to injuries such as but not limited to electrocution when opening the panel door to gain access to the breaker. After opening the door the employee reached into the energized panel and engages the breaker for the white leg.    Abatement Note: Abatement certification is required for this item (see enclosed "Certification of Corrective Action Worksheet").
Recent events (2)
  • · I (S) $850
  • · Z (S) $1700

1910.305 B01 II

Serious Gravity 1 1 instance 3 exposed
Issued
Jun 22, 2012
Abate by
Jun 25, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings were not effectively closed.    a) On or about May 8, 2012 and times prior, employees were exposed to injuries such as but not limited to electrical hazards when operating the control to move the rail cars.    Abatement Note: Abatement certification is required for this item (see enclosed "Certification of Corrective Action Worksheet").
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.23 E01

Other-than-serious 1 instance 3 exposed
Issued
Jun 22, 2012
Abate by
Jul 3, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.23(e)(1): A standard railing did not consist of an intermediate rail:    a) On or about May 8, 2012 and times prior employees were exposed to injuries from falling to the lower surface in that the stairway leading to the seed platform station was missing its intermediate rail.    Abatement Note: Abatement certification is required for this item (see enclosed "Certification of Corrective Action Worksheet").
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.106 F06

Other-than-serious 1 instance 3 exposed
Issued
Jun 22, 2012
Abate by
Jul 3, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.106(f)(6):  Class I liquids shall not be handled, drawn, or dispensed where flammable vapors may reach a source of ignition. Smoking shall be prohibited except in designated localities. "No Smoking" signs were not conspicuously posted where hazard from flammable liquid vapors is normally present:    a) On or about May 8, 2012 and times prior the employer had not posted no smoking signs where flammable vapors were present when dispensing fuels.    Abatement Note: Abatement certification is required for this item (see enclosed "Certification of Corrective Action Worksheet").
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.303 G01 I B

Other-than-serious 1 instance 3 exposed
Issued
Jun 22, 2012
Abate by
Jul 3, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(i)(B):  The width of working space in front of the electric equipment was not the width of the equipment or 762 mm (30 in.), whichever is greater. In all cases, the working space shall permit at least a 90-degree opening of equipment doors or hinged panels:    a) On or about May 8, 2012 and times prior the employer had not removed boxes from the electrical room. The boxes were blocking access to electrical panels that controlled bin A and bin number 5.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0