WAUWATOSA, WI ·
OSHA Inspection: J.C. PENNEY CORPORATION, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of J.C. PENNEY CORPORATION, INC. in 11800 W. BURLEIGH STREET, WAUWATOSA, WI 53222 (NAICS 493110). OSHA activity number 334361318.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- J.C. PENNEY CORPORATION, INC.
- Site address
- 11800 W. BURLEIGH STREET
- City
- WAUWATOSA
- State
- WI
- ZIP
- 53222
- Mailing
- 11800 W. BURLEIGH STREET, WAUWATOSA, WI 53222
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493110
- Employees
- 550
- Ownership type
- Private (A)
Citations
5 citations on file for this inspection.
1910.147 C06 II
- Issued
- Aug 30, 2012
- Abate by
- Sep 21, 2012
- Penalty
- Initial $3,000 · Current $1,500 Reduced
General-duty citation text
29 CFR 1910.147(c)(6)(ii): The employer did not certify that periodic inspections of the energy control procedures had been performed: (a) The employer did not certify that the periodic inspections have been performed.
Recent events (2)
- · I (O) $1500
- · Z (S) $3000
1910.333 A01
- Issued
- Aug 30, 2012
- Abate by
- Sep 21, 2012
- Penalty
- Initial $7,000 · Current $7,000
General-duty citation text
29 CFR 1910.333(a)(1): "Deenergized parts." Live parts to which an employee may be exposed shall be deenergized before the employee works on or near them, unless the employer can demonstrate that deenergizing introduces additional or increased hazards or is infeasible due to equipment design or operational limitations. Live parts that operate at less than 50 volts to ground need not be deenergized if there will be no increased exposure to electrical burns or to explosion due to electric arcs. (a) Employees were cleaning electrical parts which were not deenergized due to a back feed. An employee received an electrical shock.
Recent events (2)
- · I (S) $7000
- · Z (S) $7000
1910.333 B02 IV B
- Issued
- Aug 30, 2012
- Abate by
- Sep 21, 2012
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.333(b)(2)(iv)(B): Before circuits or equipment was worked as deenergized, a qualified person did not use test equipment to test the circuit elements and electrical parts of equipment to which employees would be exposed and did not verify that (a) None of the JCPenny employees used test equipment to test and verify that the circuit elements and electrical parts of equipment in the area that they were working in were deenergized before working on the parts.
Recent events (2)
- · I (S) $0
- · Z (S) $7000
1910.335 A01 I
- Issued
- Aug 30, 2012
- Abate by
- Sep 21, 2012
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed: (a) Employees were not using personal protective equipment inside the substation where potential electrical hazards existed until deenergized condition was verified by testing of all potential circuits.
Recent events (2)
- · I (S) $0
- · Z (S) $7000
1910.333 B02
- Issued
- Aug 30, 2012
- Abate by
- Sep 21, 2012
- Penalty
- Initial $7,000 · Current $3,500 Reduced
General-duty citation text
29 CFR 1910.333(b)(2): While an employee was exposed to contact with parts of fixed electric equipment or circuits which were deenergized, the circuits energizing the parts were not locked out or tagged or both in accordance with the requirements of this paragraph (b) of 29 CFR 1910.333(b)(2): (a) Employees exposed to deenergized parts of fixed electric equipment in substation 3B, did not lock out or tag the circuits energizing the parts. IN THE ALTERNATIVE 29 CFR 1910.147(f)(3)(ii)(D): Each authorized employee did not affix a personal lockout or tagout device to the group lockout device before working on the machine or equipment: (a) Employees did not put their own personal lockout or tagout device to the group lockout device on the circuits energizing substation 3B before conducting work on parts of the electric equipment.
Recent events (2)
- · I (S) $3500
- · Z (S) $7000
More inspections at J.C. Penney Corporation, INC.
View J.C. Penney Corporation, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 493110)
More inspections in WI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 334361318.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.