Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,196,249Inspections Most recent open 2026-08-20 Last loaded 2026-08-24

OSHA Inspection: FLEX-N-GATE CORPORATION

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of FLEX-N-GATE CORPORATION in 601 GUARDIAN DRIVE, URBANA, IL 61802 (NAICS 336370). OSHA activity number 334363314.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Flex-N-Gate Corporation for free Get an email when a new federal OSHA severe-injury report for Flex-N-Gate Corporation is published. One employer, no account, unsubscribe in one click.
Site address
601 GUARDIAN DRIVE
City
URBANA
State
IL
ZIP
61802
Mailing
P.O. BOX 877, URBANA, IL 61803
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
336370
Employees
358
Ownership type
Private (A)

3 citations on file for this inspection.

1910.147 C04 II

Serious Gravity 10 1 instance 2 exposed
Issued
Oct 30, 2012
Abate by
Nov 6, 2012
Penalty
Initial $7,000 · Current $4,900 Reduced
29 CFR 1910.147(c)(4)(ii):     The enrgy control procedures did not clearly and specifically outline the scope, purpose, authorization, rules and techniques to be utilized for the control of hazardous energy, including, but not limited to Items A - D of this section:    Employees working at Weld Cell #8 were exposed to the unexpected energization of the Motoman robot while conducting servicing and maintenance such as  cleaning or changing the welding tips.  The energy control procedures did not include an adequate specific statement of the intended use of the procedure, specific procedural steps for shutting down and isolating equipment to control hazardous energy, specific procedural steps for the placement and removal of lockout devices or specific requirements for testing the eqipiment to determine the effectiveness of the lockout devices.
Recent events (3)
  • · F (S) $4900
  • · C (S) $7000
  • · Z (S) $7000

1910.147 D03

Serious Gravity 10 24 instances 4 exposed
Issued
Oct 30, 2012
Abate by
Nov 6, 2012
Penalty
Initial $7,000 · Current $4,900 Reduced
29 CFR 1910.147(d)(3):     All energy isolating devices that were needed to control the energy to the machine or equipment was not physically located and operated in such a manner as to isolate the machine or equipment from the energy source:    a.  Employees working at Weld Cell #8 were exposed to the unexpected energization of the Motoman robot while conducting servicing and maintenance such as cleaning or changing the welding tips and all energy isolating devices that were needed to control the energy to the weld cell were not located so as to isolate the equipment from its energy source.    b.  Employees working at Weld Cell #14 were exposed to the unexpected energization of the FANUC robot while conducting servicing and maintenance such as cleaning or changing the welding tips and all energy isolating devices that were needed to control the energy to the weld cell were not located so as to isolate the equipment from its energy source.
Recent events (3)
  • · F (S) $4900
  • · C (S) $7000
  • · Z (S) $7000

1910.147 D04 I

Serious Gravity 10 2 instances 4 exposed
Issued
Oct 30, 2012
Abate by
Nov 6, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.147(d)(4)(i):     Lockout or tagout devices were not affixed to each energy isolating device by authorized employees:    a.  Employees working at Weld Cell #8 were exposed to the unexpected energization of the Motoman robot while conducting servicing and maintenance such as cleaning or changing the welding tips because the Telemecanique XCS Interlock safety switch had a length of chain between the access gate and the interlock key tongue which allowed the access gate to open without initiating a stop signal.  The chain installed on the access door on Weld Cell #8 allowed the gate to have an opening of nine inches without initiating the stop signal.    b.  Employees working at Weld Cell #14 were exposed to the unexpected energization of the FANUC robot while conducting servicing and maintenance such as cleaning or changing the welding tips because the Telemecanique XCS Interlock safety switch had a length of chain between the access gate and the interlock key tongue which allowed the access gate to open without initiating a stop signal.  The chain installed on the access door on Weld Cell #14 allowed the gate to have an opening of 5-1/2 inches without initiating the stop signal.
Recent events (3)
  • · F (S) $0
  • · C (S) $0
  • · Z (S) $0

View Flex-N-Gate Corporation's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 334363314.