Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,193,745Inspections Most recent open 2026-08-06 Last loaded 2026-08-10

OSHA Inspection: LEX ELECTRIC COMPANY INC.

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of LEX ELECTRIC COMPANY INC. in TEMPLE DENTAL SCHOOL 3223 N. BROAD ST, PHILADELPHIA, PA 19140 (NAICS 238210). OSHA activity number 334502937.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch LEX Electric Company INC. for free Get an email when a new federal OSHA severe-injury report for LEX Electric Company INC. is published. One employer, no account, unsubscribe in one click.
Site address
TEMPLE DENTAL SCHOOL 3223 N. BROAD ST
City
PHILADELPHIA
State
PA
ZIP
19140
Mailing
1106 N. PROVIDENCE RD. PO BOX 523, MEDIA, PA 19063
Inspection type
Federal Agency (M)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
2
Ownership type
A

2 citations on file for this inspection.

1926.416 A01

Serious Gravity 10 1 instance 1 exposed
Issued
Nov 29, 2012
Abate by
Dec 5, 2012
Penalty
Initial $7,000 · Current $7,000
29 CFR 1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means:     Temple University's Kornberg School of Dentistry, Corridor "2COR5" - An employee was exposed to an electric shock hazard while working on the shared neutral for the 277 VAC overhead corridor lighting.  The electric power circuit for an adjoining bathroom, which shared the same neutral as the corridor lighting circuit, was not de-energized.  The employee had been exposed to the hazard while changing out corridor lighting fixtures.  This change out, as conducted, had the employee disconnecting all conductors (hot, neutral, and ground) at each of three light fixtures, install a new fixture, then re-install the conductors.  The neutral for these lights was also the same neutral for an additional circuit that had not been de-energized.  On or about 5/30/2012.      Abatement certification and documentation required within 10 days after abatement date. The certification shall include a statement that abatement is complete, the date and method of abatement, and state that employees and their representatives were informed of this abatement. Abatement documentation shall include documents demonstrating that abatement is complete, such as evidence of the purchase or repair of equipment, photographic or video evidence of abatement or other written records.
Recent events (3)
  • · F (S) $7000
  • · C (S) $7000
  • · Z (S) $7000

1926.416 A03

Serious Gravity 10 1 instance 1 exposed
Issued
Nov 29, 2012
Abate by
Dec 5, 2012
Penalty
Initial $2,800 · Current $0 Reduced
29 CFR 1926.416(a)(3): Before work began, the employer did not ascertain by inquiry, direct observation, or by instruments, whether any part of an energized electric power circuit, exposed or concealed, was so located that the performance of the work could bring any person, tool, or machine into physical or electrical contact with the electric power circuit.    Temple Universitys Kornberg School of Dentistry, Corridor 2COR5  Before work began, Lex Electric did not ascertain whether any part of the shared neutral conductor for the corridor lighting circuit was completely de-energized and made safe.  An employee was exposed to 277 volts AC when working on the shared neutral for that circuit.  The shared neutral was energized via a lighting circuit that had not been de-energized.  On or about 5/30/2012.    Abatement certification and documentation required within 10 days after abatement date. The certification shall include a statement that abatement is complete, the date and method of abatement, and state that employees and their representatives were informed of this abatement. Abatement documentation shall include documents demonstrating that abatement is complete, such as evidence of the purchase or repair of equipment, photographic or video evidence of abatement or other written records.
Recent events (3)
  • · F (S) $0
  • · C (S) $2800
  • · Z (S) $2800

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 334502937.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.