SOUTH GLENS FALLS, NY ·
OSHA Inspection: SCA TISSUE NORTH AMERICA
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of SCA TISSUE NORTH AMERICA in 1 RIVER STREET, SOUTH GLENS FALLS, NY 12803 (NAICS 322121). OSHA activity number 334505138.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SCA TISSUE NORTH AMERICA
- Site address
- 1 RIVER STREET
- City
- SOUTH GLENS FALLS
- State
- NY
- ZIP
- 12803
- Mailing
- 1 RIVER STREET, SOUTH GLENS FALLS, NY 12803
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 322121
- Employees
- 277
- Ownership type
- Private (A)
Citations
4 citations on file for this inspection.
1910.303 G02 I
- Issued
- Oct 23, 2012
- Abate by
- Nov 14, 2012
- Penalty
- Initial $6,300 · Current $6,300
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): a) Building 9 - On or about July 11, 2012, an electrical junction box was not adequately mounted on the wall exposing live electrical components. b) Burner Room - On or about July 20, 2012, live electrical wires were not guarded by means of an electrical box and were setting on an accumulation of combustible paper towel dust (ST1).
Recent events (3)
- · F (S) $6300
- · C (S) $6300
- · Z (S) $6300
1910.305 G01 IV
- Issued
- Oct 23, 2012
- Abate by
- Nov 14, 2012
- Penalty
- Initial $3,825 · Current $6,300
General-duty citation text
29 CFR 1910.305(g)(1)(iv): Flexible cords and/ or cables were used for purposes prohibited by paragraphs (A) through (F) of 29 CFR 1910.305(g)(1)(iv): a) Building 9 Mezzanine - On or about July 11, 2012, an extension cord was used as permanent wiring for a mounted Dayton commercial air circulator (Serial # 11434159). b) Building 9 Mezzanine - On or about July 11, 2012, a flexible cord was used for permanently fixed lighting.
Recent events (3)
- · F (S) $6300
- · C (S) $3825
- · Z (S) $3825
1910.22 A01
- Issued
- Oct 23, 2012
- Abate by
- Nov 14, 2012
- Penalty
- Initial $6,300 · Current $6,300
General-duty citation text
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms or service rooms were not kept clean and orderly or in a sanitary condition: a) Building 9 - On or around May 30 and July 11 of 2012, structural supports, pipes, fixtures, ductwork, walls, room roofing, floors and equipment were not kept free of hazardous accumulation of combustible dust. b) Building 8 - On or around May 30, July 11 and July 20 of 2012, structural supports, pipes, fixtures, equipment and ductwork were not kept free of hazardous accumulation of combustible dust. c) Building 15 - On or around May 30 and July 20 of 2012, structural supports, pipes, fixtures, equipment and ductwork were not kept free of hazardous accumulation of combustible dust. d) Burner/Control Room - On or around May 30 and July 20 of 2012, structural supports, pipes, equipment, and ductwork were not kept free of hazardous accumulation of combustible dust.
Recent events (3)
- · F (S) $6300
- · C (S) $6300
- · Z (S) $6300
1910.307 C
- Issued
- Oct 23, 2012
- Abate by
- Nov 14, 2012
- Penalty
- Initial $6,300 · Current $0 Reduced
General-duty citation text
29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location: a) Building 9 - On or around May 30 and July 11 of 2012, employees conducted a blow down cleaning procedure for tissue paper dust, a Class II Group G Explosive Dust, suspending the dust in air. General purpose wiring, breaker panel boxes, disconnect switches, receptacles and electric motors were not dust-tight ignition proof and approved for Class II Division 1 locations. b) Building 15 - On or around May 30 and July 20, 2012, employees conduct a blow down cleaning procedure for tissue paper dust, a Class II Group G Explosive Dust, suspending the dust in the air. General purpose wiring, breaker panel boxes, disconnect switches, receptacles and electric motors were not dust-tight ignition proof and approved for Class II Division 1 locations.
Recent events (3)
- · F (S) $0
- · C (S) $6300
- · Z (S) $6300
More inspections at SCA Tissue North America
View SCA Tissue North America's full OSHA safety record →
More inspections in this industry (NAICS 322121)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 334505138.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.