CHICAGO, IL ·
OSHA Inspection: KRAFT FOODS
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of KRAFT FOODS in 7300 S. KEDZIE AVENUE, CHICAGO, IL 60629 (NAICS 311821). OSHA activity number 334548344.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- KRAFT FOODS
- Site address
- 7300 S. KEDZIE AVENUE
- City
- CHICAGO
- State
- IL
- ZIP
- 60629
- Mailing
- 7300 S. KEDZIE AVENUE, CHICAGO, IL 60629
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311821
- Employees
- 1400
- Ownership type
- Private (A)
Citations
3 citations on file for this inspection.
1910.137 B02 VIII
- Issued
- Oct 5, 2012
- Penalty
- Initial $5,000 · Current $5,000
General-duty citation text
29 CFR 1910.137(b)(2)(viii): Electrical protective equipment shall be subjected to periodic electrical tests. Test voltages and the maximum intervals between tests shall be in accordance with Table I-5 and Table I-6. Throughout facility - On or about June 15, 2012, employee(s) were required to use personal protective equipment such as rubber insulating gloves during their assigned electrical work. The employee(s) were required to work on or near voltages between 120 VAC - 480 VAC. The rubber insulating gloves were not subjected to periodic electrical tests. Employee(s) were thereby exposed to the hazards associated with live electrical parts.
Recent events (2)
- · I (S) $5000
- · Z (S) $5000
1910.303 B01 V
- Issued
- Oct 5, 2012
- Abate by
- Oct 9, 2012
- Penalty
- Initial $5,000 · Current $5,000
General-duty citation text
29 CFR 1910.303(b)(1)(v): Heating effects under all conditions of use were not examined. 2nd floor control room (Line #1) - On or about June 1, 2012, employee(s) opened the cabinet doors of six electrical panel boxes. The six electrical panel boxes contained live parts (120 VAC - 480 VAC) that were not deenergized. The cabinet doors on the six electrical panel boxes were required to remain open to balance the cooling when overheating of the indramat drives occurs. Heating effects under all conditions of use were not examined. Employee(s) were thereby exposed to the hazards associated with live electrical parts.
Recent events (2)
- · I (S) $5000
- · Z (S) $5000
1910.333 A02
- Issued
- Oct 5, 2012
- Abate by
- Oct 9, 2012
- Penalty
- Initial $5,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.333(a)(2): "Energized parts." If the exposed live parts are not deenergized (i.e., for reasons of increased or additional hazards or infeasibility), other safety-related work practices shall be used to protect employees who may be exposed to the electrical hazards involved. Such work practices shall protect employees against contact with energized circuit parts directly with any part of their body or indirectly through some other conductive object. The work practices that are used shall be suitable for the conditions under which the work is to be performed and for the voltage level of the exposed electric conductors or circuit parts. Specific work practice requirements are detailed in paragraph (c) of this section. 2nd floor control room (Line #1) - On or about June 1, 2012, employee(s) opened the cabinet doors of six electrical panel boxes. The six electrical panel boxes contained live parts (120 VAC - 480 VAC) that were not deenergized. The cabinet doors on the six electrical panel boxes were required to remained open to balance the cooling when overheating of the indramat drives occurs. Safety-related work practices were not used while the cabinet doors of the six electrical panel boxes remained open. Employee(s) were thereby exposed to the hazards associated with live electrical parts.
Recent events (2)
- · I (S) $0
- · Z (S) $5000
More inspections at Kraft Foods
View Kraft Foods's full OSHA safety record →
More inspections in this industry (NAICS 311821)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 334548344.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.