Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: EVERGREEN ELECTRICAL CORP

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of EVERGREEN ELECTRICAL CORP in 25 STATE ST, OSSINING, NY 10562 (NAICS 238210). OSHA activity number 334556164.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Evergreen Electrical Corp — free Get an email when a new federal OSHA severe-injury report for Evergreen Electrical Corp is published. One employer, no account, unsubscribe in one click.
Site address
25 STATE ST
City
OSSINING
State
NY
ZIP
10562
Mailing
133 50TH ST, BROOKLYN, NY 11232
Inspection type
Referral (C)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
1
Ownership type
A

3 citations on file for this inspection.

1926.405 A02 II B

Serious Gravity 5 1 instance 5 exposed
Issued
Oct 23, 2012
Abate by
Oct 24, 2012
Penalty
Initial $2,000 · Current $1,000 Reduced
29 CFR 1926.405(a)(2)(ii)(B): Runs of open conductors used as temporary wiring branch circuits were located where the conductors would be subject to physical damage, or the conductors were fastened at intervals exceeding 10 feet:    Location: 25 State St Ossining NY 10562    On or about 6/1/12,  a) Branch circuits running from a panel outside to inside the building were not protected from physical damage and were not fastened at least every 10 feet. They were in direct contact with metal scaffolding and a metal extension ladder used to access the scaffolding.
Recent events (2)
  • — I (S) $1000
  • — Z (S) $2000

1926.405 B01

Serious Gravity 5 3 instances 5 exposed
Issued
Oct 23, 2012
Abate by
Oct 24, 2012
Penalty
Initial $1,600 · Current $800 Reduced
29 CFR 1926.405(b)(1): Conductors entering boxes, cabinets, and fittings were not protected from abrasion, unused openings in cabinets, boxes, and fittings were not effectively closed and openings in boxes, cabinets, and fittings through which conductors entered were not effectively closed:     Location: 25 State St Ossining NY 10562    On or about 6/1/12,  a) A conductor entering a circuit breaker panel was not protected from abrasion.    b) An opening in a circuit breaker panel through which a conductor entered was not effectively closed.    c) There were several unused openings in a circuit breaker panel that were not effectively closed.
Recent events (2)
  • — I (S) $800
  • — Z (S) $1600

1926.405 E01

Serious Gravity 5 1 instance 5 exposed
Issued
Oct 23, 2012
Abate by
Oct 24, 2012
Penalty
Initial $1,600 · Current $800 Reduced
29 CFR 1926.405(e)(1): In wet locations, cabinets, cutout boxes, fittings, boxes and panelboard enclosures were not weatherproof:    Location: 25 State St Ossining NY 10562    On or about 6/1/12,  a) A circuit breaker panel designed for indoor use was installed outside exposed to the elements.
Recent events (2)
  • — I (S) $800
  • — Z (S) $1600

View Evergreen Electrical Corp's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 334556164.