CORPUS CHRISTI, TX —
OSHA Inspection: H & H IRON AND METAL, INC.
Federal Agency inspection · Safety discipline
At a glance
On , OSHA opened a federal Agency safety inspection of H & H IRON AND METAL, INC. in 3822 AGNES ST, CORPUS CHRISTI, TX 78405 (NAICS 423930). OSHA activity number 334561545.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- H & H IRON AND METAL, INC.
- Site address
- 3822 AGNES ST
- City
- CORPUS CHRISTI
- State
- TX
- ZIP
- 78405
- Mailing
- 3822 AGNES ST, CORPUS CHRISTI, TX 78405
What kind of inspection was it?
- Inspection type
- Federal Agency (M)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- Yes
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 423930
- Employees
- 37
- Ownership type
- A
Citations
9 citations on file for this inspection.
1910.176 F
- Issued
- Dec 4, 2012
- Abate by
- Dec 5, 2012
- Penalty
- Initial $4,900 · Current $2,205 Reduced
General-duty citation text
29 CFR 1910.176(f): Derail and/or bumper blocks were not provided on spur railroad tracks where a rolling car could contact other cars being worked or enter a building, work or traffic area: At this location, employees involved in a scrap metal operation were weighing rail gondola cars on the spur rail tracks inside of the employer's property. The employer did not ensure derail and/or bumper blocks were available and used to prevent coupled rail gondola cars from rolling.
Recent events (2)
- — I (O) $2205
- — Z (S) $4900
1910.180 C02
- Issued
- Dec 4, 2012
- Abate by
- Dec 5, 2012
- Penalty
- Initial $2,975 · Current $2,975
General-duty citation text
29 CFR 1910.180(c)(2): The cab(s) of truck crane(s) were not provided with a load rating chart with clearly legible letters and figures, which was easily visible to the operator while seated at the control: In the cab of the Sennebogen cranes located in the east yard, and used to pick-up scrap metal material from a large stacks and unload it into a rail gondola cars, load charts were not present: a. Sennebogen magnet, Model Number 825 b. Sennebogen grapple, Model Number 835
Recent events (2)
- — I (S) $2975
- — Z (S) $2975
1910.180 H03 IV
- Issued
- Dec 4, 2012
- Abate by
- Dec 5, 2012
- Penalty
- Initial $2,975 · Current $0 Reduced
General-duty citation text
29 CFR 1910.180(h)(3)(iv): The employer did not assure that cranes were not used for dragging loads sideways. At thiis location the employer was using cranes such as the following fitted with magnet and/or grapple attachments to drag rail cars along the spur rail tracks. a. Senneboggen magnet, Model Number 825 b. Senneboggen grapple, Model Number 835
Recent events (2)
- — I (S) $0
- — Z (S) $2975
1910.305 B01 II
- Issued
- Dec 4, 2012
- Abate by
- Dec 5, 2012
- Penalty
- Initial $1,785 · Current $2,380
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: Employees were exposed to electrical shock due to unused openings in the electrical breaker panels being left open: a. General Electric breaker panel on the inside wall at the mechanic shop. b. 110 volt electrical outlet junction box at the end of a flexible electrical cord on work table in north end of mechanic shop. c. The Tram-A-Lot baler, was in the process of waiting for a new electrical switch to be installed and the opening where the switch had been located was left open with live open with live electrical conductors present. The Square D Main Disconnect, Number 10 breaker and Number 03 breaker which supplied power to the Tram-A-Lot baler, was energized and was not locked out.
Recent events (2)
- — I (S) $2380
- — Z (S) $1785
1910.305 B02 I
- Issued
- Dec 4, 2012
- Abate by
- Dec 5, 2012
- Penalty
- Initial $2,380 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: Employees were exposed to electrical shock at an Air Master Fan, 110 volts due to the junction box being open and without a cover which permitted the live 110 volt electrical conductors to be exposed.
Recent events (2)
- — I (S) $0
- — Z (S) $2380
1910.303 B06
- Issued
- Dec 4, 2012
- Abate by
- Dec 5, 2012
- Penalty
- Initial $2,975 · Current $2,975
General-duty citation text
29 CFR 1910.303(b)(6): Conductors or equipment located in damp or wet locations; where exposed to gases, fumes, vapors, liquids, or other agents that had a deteriorating effect on the conductors or equipment; or where exposed to excessive temperatures: a. The employer had installed a rectangular electrical wiring box at the bottom of the electrical meter with the meter loop on the east side of the mechanical shop which was exposed to corrosive atmospheric conditions such as but not limited to high humidity, salty atmosphere and torential rains. This rectangular electrical wiring box served as an electrical wiring trough with live electrical conductors of 110 volts and 220 volts and was rusted through at the bottom. b. A General Electric disconnect box, was located adjacent to he electrical meter. The small lip at the bottom of the cover was completely eaten away by corrosion which did not permit a lock to be placed in order to prevent entry by unauthorized personnel into the live 200 Amp, 240 volt electrical box.
Recent events (2)
- — I (S) $2975
- — Z (S) $2975
1910.305 G01 IV A
- Issued
- Dec 4, 2012
- Abate by
- Dec 5, 2012
- Penalty
- Initial $2,380 · Current $2,380
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: Employees were exposed to electrical shock from a flexible electrical cord that was used as permanent wiring to a fluorescent fixture in a storeroom from the mechanical work shop.
Recent events (2)
- — I (S) $2380
- — Z (S) $2380
1910.305 G02 II
- Issued
- Dec 4, 2012
- Abate by
- Dec 5, 2012
- Penalty
- Initial $2,380 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(ii): Flexible cords were not used only in continuous lengths without splice or tap: Employees were exposed to electrical shock from flexible electrical cords where the exterior insulation was missing and there was no rubberized insulated tape present to cover the actual copper conductors: a. 110 volt, AC flexible electrical cord located in the workroom at the north end of the mechanic shop. b. 230 volt, DC flexible electrical cord located on the top of the magnet of the Sennebogan, Model Number 825.
Recent events (2)
- — I (S) $0
- — Z (S) $2380
1910.305 G02 III
- Issued
- Dec 4, 2012
- Abate by
- Dec 5, 2012
- Penalty
- Initial $1,785 · Current $1,785
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: At this location employees were exposed to electrical shock from: a. Flexible electrical cord which entered a Hendley & Whittemore Model Number G-2 WEG electrical box without a functional strain relief device. b. Flexible electrical metal conduit with 110 volt conductors to a two outlet receptacle adjacent to the entry on the east side of the mechanic shop.
Recent events (2)
- — I (S) $1785
- — Z (S) $1785
More inspections at H & H Iron and Metal, INC.
View H & H Iron and Metal, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 423930)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 334561545.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.