Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: DAVE HINKLE ELECTRIC INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of DAVE HINKLE ELECTRIC INC. in 200 CROSS TERRACE BLVD., CHARLESTON, WV 25309 (NAICS 238210). OSHA activity number 334568532.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Dave Hinkle Electric INC. — free Get an email when a new federal OSHA severe-injury report for Dave Hinkle Electric INC. is published. One employer, no account, unsubscribe in one click.
Site address
200 CROSS TERRACE BLVD.
City
CHARLESTON
State
WV
ZIP
25309
Mailing
4563 PLUTO ROAD, SHADY SPRING, WV 25918
Inspection type
Complaint (B)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
18
Ownership type
A

3 citations on file for this inspection.

1926.403 H

Serious Gravity 5 1 instance 4 exposed
Issued
Nov 5, 2012
Penalty
Initial $1,360 · Current $952 Reduced
29 CFR 1926.403(h):     Each service, feeder, and branch circuit was not legibly marked at its disconnecting means or overcurrent device to indicate its purpose, nor located and arranged so that the purpose was evident:    a. Adjacent to the Cafe Area: The Square D circuit breaker box used as a temporary service did not have the circuit breakers marked to identify their purpose as observed on 6-5-12.
Recent events (2)
  • — I (S) $952
  • — Z (S) $1360

1926.405 B01

Serious Gravity 5 2 instances 4 exposed
Issued
Nov 5, 2012
Penalty
Initial $0 · Current $0
29 CFR 1926.405(b)(1):     Unused openings in cabinets, boxes, and fittings were not effectively closed:    a. Temporary  Square D Circuit Breaker Box Adjacent to the Cafe: The The opening where the circuit breaker was missing was not effectively closed due to the employer covered opening with duct tape in lieu of a blank as observed on 6-5-12.    b. Temporary Square D Circuit Breaker Box Adjacent to the Cafe: The circuit breaker box had had 1 1/2 inch diameter opening in the bottom of the box that was not closed as observed on 6-5-12.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.405 A02 II B

Other-than-serious 1 instance 3 exposed
Issued
Nov 5, 2012
Penalty
Initial $0 · Current $0
29 CFR 1926.405(a)(2)(ii)(B):     Runs of open conductors used as temporary wiring branch circuits were located where the conductors would be subject to physical damage, or the conductors were fastened at intervals exceeding 10 feet:    a. Receiving Area of Building Under Construction:  The temporary Square D circuit breaker box had a yellow 12-2 with ground NM cable exiting the top of the metal box and leading up to the bar joist for a distance of approximately 18 feet without being secured as observed on 6-5-12.