WHITE PLAINS, NY ·
OSHA Inspection: NJ IRON, INC.
Programmed Related inspection · Safety discipline
At a glance
On , OSHA opened a programmed Related safety inspection of NJ IRON, INC. in 525 TARRYTOWN ROAD, WHITE PLAINS, NY 10607 (NAICS 238120). OSHA activity number 334658598.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NJ IRON, INC.
- Site address
- 525 TARRYTOWN ROAD
- City
- WHITE PLAINS
- State
- NY
- ZIP
- 10607
- Mailing
- 905 PATERSON ROAD, JACKSON, NJ 08527
What kind of inspection was it?
- Inspection type
- Programmed Related (I)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238120
- Employees
- 2
- Ownership type
- Private (A)
Citations
1 citation on file for this inspection.
1926.404 B01 II
- Issued
- Jun 20, 2012
- Abate by
- Jul 12, 2012
- Penalty
- Initial $3,500 · Current $2,100 Reduced
General-duty citation text
1926.404(b)(1)(ii): Ground-fault circuit interrupters. All 120-volt, single-phase 15- and 20-ampere receptacle outlets on construction sites, which are not a part of the permanent wiring of the building or structure and which are in use by employees, did not have approved ground-fault circuit interrupters for personnel protection. Receptacles on a two-wire, single-phase portable or vehicle-mounted generator rated more than 5kW, where the circuit conductors of the generator are insulated from the generator frame and all other grounded surfaces, were not protected with ground-fault circuit interrupters: a) Employees were using a 10.5kW generator without GFCI protection while operating electric angle grinders. 525 Tarrytown Road, observed on or about 12 June 2012.