OSHA Inspection: SHOWALTER INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of SHOWALTER INC. in 501 WILEY, SWINK, CO 81077 (NAICS 424510). OSHA activity number 334665791.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Showalter INC. for free Get an email when a new federal OSHA severe-injury report for Showalter INC. is published. One employer, no account, unsubscribe in one click.
Establishment
SHOWALTER INC.
Site address
501 WILEY
City
SWINK
State
CO
ZIP
81077
Mailing
P.O. BOX 265, SWINK, CO 81077
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424510
Employees
4
Ownership type
A

5 citations on file for this inspection.

1910.303 B01 II

Serious Gravity 5 1 instance 3 exposed
Issued
Aug 16, 2012
Abate by
Aug 23, 2012
Penalty
Initial $1,700 · Current $850 Reduced
29 CFR 1910.303(b)(1)(ii):  Electrical equipment was not free from recognized hazards, based on the mechanical strength and durability, including, for parts designed to enclose and protect other equipment, the adequacy of the protection thus provided:    a)  On or about May 4, 2012 and at times prior, Showalter Inc. did not ensure that employees were protected from electrical hazards.  The electrical switches and breakers were installed in cabinets made of wood.  The wood is not rated to be adequate protection for these electrical components.
Recent events (2)
  • · I (S) $850
  • · Z (S) $1700

1910.303 B08 I

Serious Gravity 5 1 instance 3 exposed
Issued
Aug 16, 2012
Abate by
Aug 23, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(8)(i):  Electric equipment was not firmly secured to the surface on which it was to be mounted:    a)  On or about May 4, 2012 and at times prior, Showalter Inc did not ensure that employees were protected from electrical hazards.  A J-box at the drying unit was not secured.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.303 D

Serious Gravity 5 1 instance 3 exposed
Issued
Aug 16, 2012
Abate by
Aug 23, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(d):  Arcing parts. Parts of electric equipment that in ordinary operation produce arcs, sparks, flames, or molten metal were not enclosed or separated and isolated from all combustible material.    a)  On or about May 4, 2012 and at times prior, Showalter Inc. did not ensure that employees were protected from electrical hazards.  Combustable items such as gear oil, rags, and plastic feed bags were stored inside the wooden boxes which housed the switches and breakers for the receiving pit area.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.305 G01 IV B

Serious Gravity 5 1 instance 3 exposed
Issued
Aug 16, 2012
Abate by
Aug 23, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(B):  Flexible cords and cables were run through holes in walls, ceilings, or floors:    a)  On or about May 4, 2012 and at times prior, Showalter Inc. did not ensure that employees were protected from electrical hazards.  Flexible cords were run through the plywood walls of the switches and breakers box.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.305 G02 II

Serious Gravity 5 1 instance 3 exposed
Issued
Aug 16, 2012
Abate by
Aug 23, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(ii):  Hard-service cord and junior hard-service cord No. 14 and larger were repaired by splicing, which did not retain the insulation, outer sheath properties, and usage characteristics of the cord that was spliced:    a)  On or about May 4, 2012 and at times prior, Showalter Inc. did not ensure that employees were protected from electrical hazards.  The tape used on the outside of the splice was not rated for use in wet and damp locations.  Wrapping it around the cord did not bring the outer insulation of the cord to manufacturers specifications.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 334665791.