SEATTLE, WA ·
OSHA Inspection: NATIONAL PARK SERVICE PACIFIC WEST REGIONAL OFFICE, SAFETY & HEALTH
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of NATIONAL PARK SERVICE PACIFIC WEST REGIONAL OFFICE, SAFETY & HEALTH in 909 FIRST AVE, 5TH FLOOR SOUTH, SEATTLE, WA 98104 (NAICS 712190). OSHA activity number 334681574.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Site address
- 909 FIRST AVE, 5TH FLOOR SOUTH
- City
- SEATTLE
- State
- WA
- ZIP
- 98104
- Mailing
- 909 FIRST AVE, 5TH FLOOR, SEATTLE, WA 98104
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 712190
- Employees
- 2
- Ownership type
- Federal government (D)
Citations
4 citations on file for this inspection.
1910.36 G02
- Issued
- Jul 12, 2012
- Abate by
- Aug 23, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points: a) The Hallway adjacent to the Storage Room, where the aisle way to the exit access measured 21 1/2 inches in width.
Recent events (1)
- · Z (O) $0
1910.37 B05
- Issued
- Jul 12, 2012
- Abate by
- Aug 23, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g. closet): a) Storage Room, where the door to the storage room was not equipped with signage.
Recent events (1)
- · Z (O) $0
1910.159 C10
- Issued
- Jul 12, 2012
- Abate by
- Aug 23, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.159(c)(10): The minimum vertical clearance of 18 inches between automatic sprinkler systems sprinklers and the material below was not maintained: a) Supply Room, where placement of carpet squares on the storage shelf created a 15 inch clearance beneath the sprinkler head.
Recent events (1)
- · Z (O) $0
1960.25 C
- Issued
- Jul 12, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1960.25(c): The Agency did not inspect annually, all areas in each workplace, including office operations: a) Facility, where annual inspections had not been conducted.
Recent events (1)
- · Z (O) $0
More inspections in this industry (NAICS 712190)
More inspections in WA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 334681574.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.