Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,197,549Inspections Most recent open 2026-08-27 Last loaded 2026-08-31

OSHA Inspection: NELLIS AIR FORCE BASE, UTILITIES MAINTENANCE SHOP

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NELLIS AIR FORCE BASE, UTILITIES MAINTENANCE SHOP in CEOIU, BUILDING 874, NELLIS AFB, NV 89191 (NAICS 928110). OSHA activity number 334681582.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Nellis AIR Force Base, Utilities Maintenance Shop for free Get an email when a new federal OSHA severe-injury report for Nellis AIR Force Base, Utilities Maintenance Shop is published. One employer, no account, unsubscribe in one click.
Site address
CEOIU, BUILDING 874
City
NELLIS AFB
State
NV
ZIP
89191
Mailing
HEADQUARTERS 99TH AIR BASE WING (ACC) BUILDING 7, NELLIS AFB, NV 89191
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
928110
Employees
10
Ownership type
Federal government (D)

5 citations on file for this inspection.

1910.147 C05 I

Serious Gravity 5 20 instances 10 exposed
Issued
Oct 17, 2012
Abate by
Nov 6, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(5)(i): Locks, tags, chains, wedges, key blocks, adapter pins, self-locking fasteners, or other hardware were not provided by the employer for isolating, securing or blocking of machines or equipment from energy sources:    a) At the Utilities Maintenance Shop, lock was not available to lock out energy isolating device at inspectors test valve.     b) At the Wellhead house, building 563 lock was not available to lock out energy isolating device at electrical panel providing service to the wellhead.
Recent events (1)
  • · Z (S) $0

1910.147 C05 II B

Serious Gravity 5 20 instances 10 exposed
Issued
Oct 17, 2012
Abate by
Nov 6, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(5)(ii)(B): Lockout and tagout devices were not standardized within the facility in at least one of the following criteria: Color; shape; or size; and additionally, in the case of tagout devices, print and format shall be standardized.    a) At the Utilities Shop, Tagout devices located in Lock Out Tagout kit were not standarized as to color and size, print and format. Maintenance tags with black on white background, White Hazard Notification - Identification tags with black lettering, Out of Order tags with white lettering on black back ground, Do Not Start tags with white lettering on red circle back ground. No tags had "DANGER, Do Not Start" or similar warning printed on the tag.
Recent events (1)
  • · Z (S) $0

1910.147 C07 I A

Serious Gravity 5 20 instances 10 exposed
Issued
Oct 17, 2012
Abate by
Nov 6, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(7)(i)(A): Authorized employee(s) were not trained on the recognition of applicable hazardous energy sources, the type and magnitude of the energy available in the workplace, and the methods and means necessary for energy isolatation.:    a) At the well head building employees had not been trained on the specific methods and energy isolating devices to lock out the electrical panel for the well pump.     b) At the Utilities maintenance shop, employees had not been trained on the specific methods and energy isolating devices for the inspectors test valve.
Recent events (1)
  • · Z (S) $0

1910.303 G02 I

Serious Gravity 5 1 instance 10 exposed
Issued
Oct 17, 2012
Abate by
Nov 6, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures.:    a) At the Utilities Shop lunch and break area an operating DELL 1000 computer sitting on floor with the side cover removed exposing live parts.
Recent events (1)
  • · Z (S) $0

1910.157 C04

Other-than-serious 1 instance 10 exposed
Issued
Oct 17, 2012
Abate by
Nov 6, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(4): Portable fire extinguishers were not maintained in a fully charged and operable condition:    a) At the Utilities Maintenance Shop yard, next to entrance door of flammable storage shed, a portable fire extinguisher was in the over charge condition and exposed to direct sunlight.
Recent events (1)
  • · Z (O) $0

View Nellis AIR Force Base, Utilities Maintenance Shop's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 334681582.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.