NEW LONDON, CT —
OSHA Inspection: KINDRED NURSING AND REHABILITATION - CROSSINGS WEST
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of KINDRED NURSING AND REHABILITATION - CROSSINGS WEST in 89 VIETS STREET, NEW LONDON, CT 06320 (NAICS 623110). OSHA activity number 334701182.
Where did this inspection happen?
- Establishment
- KINDRED NURSING AND REHABILITATION - CROSSINGS WEST
- Site address
- 89 VIETS STREET
- City
- NEW LONDON
- State
- CT
- ZIP
- 06320
- Mailing
- 89 VIETS STREET, NEW LONDON, CT 06320
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 623110
- Employees
- 64
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.147 C04 I
- Issued
- Jul 19, 2012
- Abate by
- Aug 30, 2012
- Penalty
- Initial $1,785 · Current $1,785
General-duty citation text
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section: Laundry: The specific lockout procedure provided for gas-fired dryers did not include natural gas as an energy source. Also, dryers were not locked out during lint removal operations that required that the front control panel be removed for access.
Recent events (1)
- — Z (S) $1785
1910.213 B03
- Issued
- Jul 19, 2012
- Abate by
- Aug 30, 2012
- Penalty
- Initial $2,380 · Current $2,380
General-duty citation text
29 CFR 1910.213(b)(3): Provisions were not made to prevent woodworking machine(s) from automatically restarting upon restoration of power after power failure: Maintenance Shop: A Ryobi nine inch vertical band saw was not provided with a drop out type starter or equivalent to prevent the machine from restarting in the event of a power outage with subsequent restoration of power while the machine had been running.
Recent events (1)
- — Z (S) $2380
1910.304 G05
- Issued
- Jul 19, 2012
- Penalty
- Initial $2,975 · Current $2,975
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: Dietary: Continuity could not be found between the machine frame of the Hobart Model A-200 mixer and the ground prong on the plug. The grounding conductor provided in the power cord was found to be loose at the connection to the machine frame.
Recent events (1)
- — Z (S) $2975
1910.305 B01 II
- Issued
- Jul 19, 2012
- Penalty
- Initial $1,515 · Current $1,515
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: Main Electrical Room: Three knockout openings were left uncovered on the left side of the GE main disconnect panel.
Recent events (1)
- — Z (S) $1515
1910.1030 C01 II B
- Issued
- Jul 19, 2012
- Abate by
- Aug 30, 2012
- Penalty
- Initial $2,380 · Current $2,380
General-duty citation text
29 CFR 1910.1030(c)(1)(ii)(B): The Exposure Control Plan did not contain the schedule and method of implementation for paragraphs (d) Methods of Compliance of this standard: Company: The Exposure Control Plan had not been updated to reflect the current blood spill clean-up procedures in effect in the facility in that: 1. The "Blood Spills" portion of the Exposure Control Plan required the use of a diluted bleach solution instead of blood spill kits. 2. Housekeeping staff was listed as the secondary group responsible for cleaning blood spills. At the time of the inspection, housekeeping staff was employed by an outside contractor was no longer responsible to clean blood spills.
Recent events (1)
- — Z (S) $2380
1910.1030 G02 V
- Issued
- Jul 19, 2012
- Abate by
- Aug 30, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1030(g)(2)(v): Employees were not provided additional training when changes such as modification of tasks or procedures or institution of new tasks or procedures affected the employee's occupational exposure: Company: The facilitys current blood spill clean-up procedure had not been adequately conveyed to staff after the responsibility to clean blood spills had been taken from the contract housekeeping staff and placed with nursing staff.
Recent events (1)
- — Z (S) $0
1910.37 B02
- Issued
- Jul 19, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit": Main Electrical Room: The exterior exit door had not been provided with an EXIT sign.
Recent events (1)
- — Z (O) $0
More inspections in this industry (NAICS 623110)
More inspections in CT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 334701182.