Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: DAVIS, PICKERING & CO., INC.

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of DAVIS, PICKERING & CO., INC. in 235 N. PUTNAM ST., MARIETTA, OH 45750 (NAICS 238210). OSHA activity number 334705431.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Davis, Pickering & CO., INC. — free Get an email when a new federal OSHA severe-injury report for Davis, Pickering & CO., INC. is published. One employer, no account, unsubscribe in one click.
Site address
235 N. PUTNAM ST.
City
MARIETTA
State
OH
ZIP
45750
Mailing
165 ENTERPRISE DRIVE, MARIETTA, OH 45750
Inspection type
Unprogrammed Other (I)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
90
Ownership type
A

3 citations on file for this inspection.

1926.403 D01

Serious Gravity 1 3 instances 4 exposed
Issued
Aug 2, 2012
Abate by
Aug 9, 2012
Penalty
Initial $1,785 · Current $1,250 Reduced
29 CFR 1926.403(d)(1):     Mounting. Electric equipment shall be firmly secured to the surface on which it is mounted. Wooden plugs driven into holes in masonry, concrete, plaster, or similar materials shall not be used.    a.    On the first floor where energized electrical panels were located, The electrical panels were not securely mounted to the wall but were hung from wires on the ceiling thereby exposing employees to a contact hazard.    b.     On the second floor where energized eletrical panels, were located, the electrical panels were not securely mounted to the wall but were hung from wires on the ceiling thereby exposing employees to a contact hazard.
Recent events (2)
  • — I (S) $1249.5
  • — Z (S) $1785

1926.405 G02 V

Serious Gravity 1 1 instance 3 exposed
Issued
Aug 2, 2012
Penalty
Initial $1,785 · Current $1,250 Reduced
29 CFR 1926.405(g)(2)(v):     Cords passing through holes. Flexible cords and cables shall be protected by bushings or fittings where passing through holes in covers, outlet boxes, or similar enclosures.    a.     In the teledata room 1/B where the temporary electrical was connected, the tempoary electrical cord coming out of the electrical panel was pulled from the panel and not provided with bushings thereby exposing employees to a contact hazard.
Recent events (2)
  • — I (S) $1249.5
  • — Z (S) $1785

1926.405 J01 I

Serious Gravity 1 1 instance 3 exposed
Issued
Aug 2, 2012
Penalty
Initial $1,785 · Current $1,250 Reduced
29 CFR 1926.405(j)(1)(i):     Live parts. Fixtures, lampholders, lamps, rosettes, and receptacles shall have no live parts normally exposed to employee contact. However, rosettes and cleat-type lampholders and receptacles located at least 8 feet (2.44 m) above the floor may have exposed parts.    a.     On the fourth foor, Area C the temporary lighting was installed 20 inches from the floor where it was connected to the electrical outlet thereby exposing employees to a contact hazard.
Recent events (2)
  • — I (S) $1249.5
  • — Z (S) $1785

View Davis, Pickering & CO., INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 334705431.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.