ROCHESTER, NY —
OSHA Inspection: CARUSO ELECTRIC INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of CARUSO ELECTRIC INC. in 1180 JEFFERSON ROAD, ROCHESTER, NY 14623 (NAICS 238210). OSHA activity number 334785425.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CARUSO ELECTRIC INC.
- Site address
- 1180 JEFFERSON ROAD
- City
- ROCHESTER
- State
- NY
- ZIP
- 14623
- Mailing
- 608 TRABOLD ROAD, ROCHESTER, NY 14624
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 8
- Ownership type
- A
Citations
4 citations on file for this inspection.
1926.28 A
- Issued
- Sep 17, 2012
- Abate by
- Oct 17, 2012
- Penalty
- Initial $2,800 · Current $1,000 Reduced
General-duty citation text
29 CFR 1926.28(a): Appropriate personal protective equipment was not worn by employee(s) in all operations where there was exposure to hazardous conditions: a) On or about 6/19/12 in the Boiler Room at Sutherland Global Services Rochester, New York; employee removed the front protective covers on Section 1 of the ( 480Y/277V, 3 phase 4 wire 1600 amp ) Challenger "Power Master" switchboard exposing energized electrical parts and was required to wear a faceshield, flame resistant clothing, hearing protection and voltage rated protective gloves prior to placing a 30 amp circuit breaker far enough into the #3 slot on the energized switchboard causing an arc flash/ arc blast. Abatement Documentation
Recent events (3)
- — J (S) $1000
- — C (S) $2800
- — Z (S) $2800
1926.95 A
- Issued
- Sep 17, 2012
- Abate by
- Oct 17, 2012
- Penalty
- Initial $2,160 · Current $0 Reduced
General-duty citation text
29 CFR 1926.95(a): Personal protective equipment, including personal protective equipment for extremities ( hands and arms ) was not maintained in reliable condition when it was necessary by reason of hazards of the environment, encountered in a manner capable of causing injury or impairment in the function of any part of the body through physical contact. a) On or about 6/19/12 at Sutherland Global Services Rochester, New York; voltage rated gloves ( White Rubber Corp - Size 10, Class 0 ) were last tested approximately five years ago. No Abatement Documentation
Recent events (3)
- — J (S) $0
- — C (S) $2160
- — Z (S) $2160
1926.416 A01
- Issued
- Sep 17, 2012
- Abate by
- Oct 17, 2012
- Penalty
- Initial $2,800 · Current $500 Reduced
General-duty citation text
29 CFR 1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means: a) On or about 6/19/12 in the Boiler Room at Sutherland Global Services Rochester, New York; employee removed the front covers for circuit breakers #2 & #4 on Section 1 of the ( 480Y/277V, 3 phase 4 wire 1600 amp ) Challenger "Power Master" switchboard exposing energized electrical parts without providing any type of protective cover or guarding against contact with these parts. Abatement Documentation
Recent events (3)
- — J (S) $500
- — C (S) $2800
- — Z (S) $2800
1926.416 A03
- Issued
- Sep 17, 2012
- Abate by
- Oct 30, 2012
- Penalty
- Initial $2,800 · Current $500 Reduced
General-duty citation text
29 CFR 1926.416(a)(3): Employer did not advise employees of the the hazards involved and the protective measures to be taken: a) On or about 6/19/12 in the Boiler Room at Sutherland Global Services Rochester, New York; employee (1) removed the three front covers on Section 1 of the ( 480Y/277V, 3 phase 4 wire 1600 amp ) Challenger "Power Master" switchboard and began to install a 30 amp circuit breaker into the #3 slot of the energized switchboard when an arc flash/arc blast occurred. Employee (2) was assisting employee (1) by holding a flashlight to illuminate the work area in proximity to the energized switchboard. Employee (1) did not advise employee (2) about the arc flash/arc blast hazards of working on or near energized electrical equipment nor the protective equipment to be worn. Abatement Documentation
Recent events (3)
- — J (S) $500
- — C (S) $2800
- — Z (S) $2800
More inspections in this industry (NAICS 238210)
More inspections in NY
Source