Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: CVM ELECTRIC, INC.

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of CVM ELECTRIC, INC. in 998 BROADWAY STREET, BUFFALO, NY 14212 (NAICS 238210). OSHA activity number 334826807.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch CVM Electric, INC. — free Get an email when a new federal OSHA severe-injury report for CVM Electric, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
CVM ELECTRIC, INC.
Site address
998 BROADWAY STREET
City
BUFFALO
State
NY
ZIP
14212
Mailing
220 DINGENS STREET, BUFFALO, NY 14206
Inspection type
Unprogrammed Other (I)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
4
Ownership type
A

2 citations on file for this inspection.

1926.403 I02 I

Serious Gravity 5 1 instance 2 exposed
Issued
Jul 16, 2012
Penalty
Initial $1,600 · Current $800 Reduced
29 CFR 1926.403(i)(2)(i):     Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures, nor by any of the means listed in subparagraphs (A) through (D) of this paragraph.    a) On or about 6/25/12, on Aldi's Construction Site, in the Utility Room, 998 Broadway St., Buffalo, NY: An uncovered rectangular opening for the light switch contained the conductors for the room lighting. An approximately 6 inch long cord with an electrical plug attached to one end, was connected to the conductors inside the switch opening with wire  nuts. The plug & short cord hung out of the opening. One end of an extension cord was connected to a 120 volt-ac receptacle on a generator, and the "hanging" plug was plugged into the other end of that extension cord, backfeeding the room lights. Live electrical conductors were exposed.    NO ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $800
  • — Z (S) $1600

1926.1053 B04

Deleted Serious Gravity 1 1 instance 1 exposed
Issued
Jul 16, 2012
Penalty
Initial $1,020 · Current $0 Reduced
29 CFR 1926.1053(b)(4):     Ladder(s) were used for purposes other than the purpose for which they were designed:      a) On or about 6/25/12, on Aldi's Construction Site, 998 Broadway St., Buffalo, NY: Employee stood on the fourth and fifth steps of an unopened stepladder laid against the west wall on the outside of the building to drill some holes in the wall.    NO ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $0
  • — Z (S) $1020

View CVM Electric, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 334826807.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.