LEESVILLE, LA —
OSHA Inspection: PROGRESSIVE INTEREST INC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of PROGRESSIVE INTEREST INC in 1304 ENTRANCE RD., LEESVILLE, LA 71459 (NAICS 238210). OSHA activity number 334831583.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- PROGRESSIVE INTEREST INC
- Site address
- 1304 ENTRANCE RD.
- City
- LEESVILLE
- State
- LA
- ZIP
- 71459
- Mailing
- 6105 MAPLE ST, HOUSTON, TX 77074
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 4
- Ownership type
- A
Citations
2 citations on file for this inspection.
1926.405 B01
- Issued
- Jul 30, 2012
- Abate by
- Aug 9, 2012
- Penalty
- Initial $2,400 · Current $2,400
General-duty citation text
29 CFR 1926.405(b)(1): Conductors entering boxes, cabinets, or fittings. Conductors entering boxes, cabinets, or fittings shall be protected from abrasion, and openings through which conductors enter shall be effectively closed. Unused openings in cabinets, boxes, and fittings shall also be effectively closed. a) On or about June 20, 2012; at the center of the jobsite, employees were allowed to use an electrical cabinet which had an unused opening that was not effectively closed. The electrical cabinet along with multiple electrical outlets that it powered were affixed to a temporary power distribution panel that employees used to power their tools. Progressive Interest, Inc. was previously cited for a violation of this occupational safety and health standard or its equivalent standard [29 CFR 1926.405(b)(1)], which was contained in OSHA inspection number 313029522, citation number 01, item number 002 and was affirmed as a final order on 10/18/2010, with respect to a workplace located at 1731 W. Prien Lake Rd., Lake Charles, LA 70605.
Recent events (3)
- — F (R) $2400
- — C (R) $2400
- — Z (R) $2400
1926.405 D
- Issued
- Jul 30, 2012
- Abate by
- Aug 9, 2012
- Penalty
- Initial $1,200 · Current $1,200
General-duty citation text
29 CFR 1926.405(d): Switchboards and panelboards. Switchboards that have any exposed live parts shall be located in permanently dry locations and accessible only to qualified persons. Panelboards shall be mounted in cabinets, cutout boxes, or enclosures designed for the purpose and shall be dead front. However, panelboards other than the dead front externally-operable type are permitted where accessible only to qualified persons. Exposed blades of knife switches shall be dead when open. a) On or about June 20, 2012; at the center of the jobsite, employees were allowed to use an energized panelboard mounted in a cabinet which did not have adequate dead front. The electrical cabinet containing the energized panelboard along with multiple electrical outlets that it powered were affixed to a temporary power distribution panel that employees used to power their tools.
Recent events (3)
- — F (S) $1200
- — C (S) $1200
- — Z (S) $1200
More inspections at Progressive Interest INC
View Progressive Interest INC's full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in LA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 334831583.