KEARNY, NJ ·
OSHA Inspection: DARELLA ELECTRICAL, INC
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of DARELLA ELECTRICAL, INC in 150 HARRISON AVE, KEARNY, NJ 07032 (NAICS 238210). OSHA activity number 334881992.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- DARELLA ELECTRICAL, INC
- Site address
- 150 HARRISON AVE
- City
- KEARNY
- State
- NJ
- ZIP
- 07032
- Mailing
- 21 EAST 16TH STREET, PATERSON, NJ 07501
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 6
- Ownership type
- Private (A)
Citations
6 citations on file for this inspection.
1926.95 A
- Issued
- Jul 31, 2012
- Penalty
- Initial $2,800 · Current $1,400 Reduced
General-duty citation text
29 CFR 1926.95(a): Protective equipment, including personal protective equipment for eyes, face, head, and extremities, protective clothing, respiratory devices, and protective shields and barriers, was not provided, used, and maintained in a sanitary and reliable condition wherever it was necessary by reason of hazards of processes or environment, chemical hazards, radiological hazards, or mechanical irritants encountered in a manner capable of causing injury or impairment in the function of any part of the body through absorption, inhalation or physical contact: a) 150 Harrison Ave, Kearny, NJ. Employee working inside junction box on live wires was no provided personal protective gloves, thereby causing second degree burn on his left hand. Violation occurred on or about 06/22/2012.
Recent events (3)
- · F (S) $1400
- · C (S) $2800
- · Z (S) $2800
1926.403 I02 I
- Issued
- Jul 31, 2012
- Penalty
- Initial $2,800 · Current $1,400 Reduced
General-duty citation text
29 CFR 1926.403(i)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures, nor by any of the means listed in subparagraphs (A) through (D) of this paragraph. a) Electrical room. Electrical panels on the jobsite did not have covers, thereby exposing employees to potential electrical hazards. Violation observed on or about 06/22/2012.
Recent events (3)
- · F (S) $1400
- · C (S) $2800
- · Z (S) $2800
1926.403 I02 III
- Issued
- Jul 31, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.403(i)(2)(iii): Entrances to rooms and other guarded locations containing exposed live parts operating at 600 volts, nominal, or less were not marked with conspicuous warning signs forbidding unqualified persons to enter: a) 150 Harrison Ave, Kearny, NJ. The door leading to the electrical room located within the building, were not marked or guarded limiting access of unqualified personnel. Violation observed on or about 06/22/2012.
Recent events (3)
- · F (S) $0
- · C (S) $0
- · Z (S) $0
1926.416 A01
- Issued
- Jul 31, 2012
- Penalty
- Initial $2,800 · Current $1,400 Reduced
General-duty citation text
29 CFR 1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means: Junction box. Employee was exposed to electric shock as he was working in proximity of live parts while tracing out circuits in the junction box/panel. Violation occurred on or about 06/22/2012.
Recent events (3)
- · F (S) $1400
- · C (S) $2800
- · Z (S) $2800
1926.416 A03
- Issued
- Jul 31, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.416(a)(3): Before work began, the employer did not ascertain by inquiry, direct observation, or by instruments, whether any part of an energized electric power circuit, exposed or concealed, was so located that the performance of the work could bring any person, tool, or machine into pysical or electrical contact with the electric power circuit. a) Vision center inside walmart. The employer had not ascertained whether its employees were protected from coming into contact with energized parts as found in the junction box. Violation observed on or about 06/22/2012.
Recent events (3)
- · F (S) $0
- · C (S) $0
- · Z (S) $0
1926.403 H
- Issued
- Jul 31, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.403(h): Each service, feeder, and branch circuit was not legibly marked at its disconnecting means or overcurrent device to indicate its purpose, nor located and arranged so that the purpose was evident: a) Electrical room. The control panel in the main floor, electrical room, was not properly marked identifying the location of outlets/devices being energized. Violation observed on or about 06/22/2012.
Recent events (3)
- · F (O) $0
- · C (O) $0
- · Z (O) $0
More inspections in this industry (NAICS 238210)
More inspections in NJ
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 334881992.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.