BROCKPORT, NY —
OSHA Inspection: DUKES PROPERTY DEVELOPMENT, LLC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of DUKES PROPERTY DEVELOPMENT, LLC in 350 NEW CAMPUS DRIVE BROCKPORT COLLEGE, BROCKPORT, NY 14420 (NAICS 236115). OSHA activity number 334908803.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- DUKES PROPERTY DEVELOPMENT, LLC
- Site address
- 350 NEW CAMPUS DRIVE BROCKPORT COLLEGE
- City
- BROCKPORT
- State
- NY
- ZIP
- 14420
- Mailing
- 6485 BUFFALO ROAD, CHURCHVILLE, NY 14428
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 236115
- Employees
- 4
- Ownership type
- A
Citations
2 citations on file for this inspection.
1926.404 B01 II
- Issued
- Jul 31, 2012
- Penalty
- Initial $1,020 · Current $1,020
General-duty citation text
29 CFR 1926.404(b)(1)(ii): Ground-fault circuit interrupters. All 120-volt, single-phase 15- and 20-ampere receptacle outlets on construction sites, which are not a part of the permanent wiring of the building or structure and which are in use by employees, shall have approved ground-fault circuit interrupters for personnel protection. Receptacles on a two-wire, single-phase portable or vehicle-mounted generator rated not more than 5kW, where the circuit conductors of the generator are insulated from the generator frame and all other grounded surfaces, need not be protected with ground-fault circuit interrupters. On or about 06/28/12, at the Tuttle North building, at Brockport College, a McCulloch generator, without GFCI protection was in use. NO ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
- — Z (S) $1020
1926.404 B01 III C
- Issued
- Jul 31, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.404(b)(1)(iii)(C): Each cord set, attachment cap, plug and receptacle of cord sets, and any equipment connected by cord and plug, except cord sets and receptacles which are fixed and not exposed to damage, shall be visually inspected before each day's use for external defects, such as deformed or missing pins or insulation damage, and for indications of possible internal damage. Equipment found damaged or defective shall not be used until repaired. On or about 06/28/12, at the Tuttle North building, a cord set was in use with a missing ground pin. NO ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
- — Z (O) $0
More inspections in this industry (NAICS 236115)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 334908803.