YORK, NE —
OSHA Inspection: YORK COLD STORAGE 1, LLC
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of YORK COLD STORAGE 1, LLC in 402 COMMERCE STREET, YORK, NE 68467 (NAICS 493120). OSHA activity number 334913787.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- YORK COLD STORAGE 1, LLC
- Site address
- 402 COMMERCE STREET
- City
- YORK
- State
- NE
- ZIP
- 68467
- Mailing
- 402 COMMERCE STREET, YORK, NE 68467
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493120
- Employees
- 53
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.119 J02
- Issued
- Nov 6, 2012
- Abate by
- Dec 9, 2012
- Penalty
- Initial $3,850 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(j)(2): The employer did not establish or implement written procedures to maintain the on-going integrity of process equipment: 402 Commerce Street, York, NE 68467 (Site-Wide): The employer did not establish or implement written procedures to maintain the on-going integrity of process equipment, including but not limited to; testing internal pipe thickness. No procedures had been developed in order to test the internal corrosion rate on pipe in the ammonia system. A recognized and generally accepted good engineering practice from the IIAR (International Institute of Ammonia Refrigeration) Bulletin 110 states that deeper pitting of metal, where considered by subjective assessment to be greater than 10% of original wall thickness should be checked accurately by using techniques such as ultrasonic measurements. Abatement certification and abatement documentation is required for this violation. The abatement certification sheet is enclosed.
Recent events (2)
- — I (S) $0
- — Z (S) $3850
1910.119 J05
- Issued
- Nov 6, 2012
- Abate by
- Jan 11, 2013
- Penalty
- Initial $3,850 · Current $3,080 Reduced
General-duty citation text
29 CFR 1910.119(j)(5): The employer did not correct deficiencies in equipment that were outside acceptable limits (defined by the process safety information on paragraph (d) of this section) in a safe and timely manner when necessary means where taken to assure safe operation: 402 Commerce Street, York, NE 68467 (Site-Wide): The employer did not change out 22 pressure relief valves (PRVs) on 5-year intervals as required. These include; but are not limited to; 1) LSC - 1 Pressure relief valve 80. A recognized and generally accepted good engineering practice from the IIAR (International Institute of Ammonia Refrigeration) Bulletin 110, Section 6.6.3 Revised states that pressure relief devices shall be replaced or recertified in accordance with one of these three options: 1. Every five (5) years from the date of installation. IIAR originally recommended (in 1978) that pressure relief valves be replaced every five years from the date of installation. This recommendation represents good engineering practice considering the design and performance of pressure relief devices; or 2. An alternative to the prescriptive replacement interval, i.e., five years, can be developed based on documented in-service relief valve life for specific applications using industry accepted good practices of relief valve evaluation; or 3. The manufacturers recommendations on replacement frequency of pressure relief devices shall be followed. Abatement certification and abatement documentation is required for this violation. The abatement certification sheet is enclosed.
Recent events (2)
- — I (S) $3080
- — Z (S) $3850
1910.134 E01
- Issued
- Nov 6, 2012
- Abate by
- Jan 11, 2013
- Penalty
- Initial $3,850 · Current $3,080 Reduced
General-duty citation text
29 CFR 1910.134(e)(1): The employer shall provide a medical evaluation to determine the employee's ability to use a respirator, before the employee is fit tested or required to use the respirator in the workplace. The employer may discontinue an employee's medical evaluations when the employee is no longer required to use a respirator: 402 Commerce Street, York, NE 68467 (Site-Wide): The employer did not provide medical evaluations prior to requiring employees to use full-face respirators in the workplace. Abatement certification is required for this violation. The abatement certification sheet is enclosed with these citations.
Recent events (2)
- — I (S) $3080
- — Z (S) $3850
1910.134 F01
- Issued
- Nov 6, 2012
- Abate by
- Jan 11, 2013
- Penalty
- Initial $3,850 · Current $3,080 Reduced
General-duty citation text
29 CFR 1910.134(f)(1): The employer did not ensure that employee(s) required to use a tight-fitting facepiece respirator passed the appropriate qualitative fit test (QLFT) or quantitative fit test (QNFT): 402 Commerce Street, York, NE 68467 (): Employees were required to use full-face respirators to turn off an ammonia valve prior to the employer ensuring they passed the appropriate qualitative fit test (QLFT) or quantitative fit test (QNFT). Abatement certification is required for this violation. The abatement certification sheet is enclosed with these citations.
Recent events (2)
- — I (S) $3080
- — Z (S) $3850
More inspections at York Cold Storage 1, LLC
View York Cold Storage 1, LLC's full OSHA safety record →
More inspections in this industry (NAICS 493120)
More inspections in NE
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 334913787.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.