OSHA Inspection: POSTAL SERVICE US ROANOKE

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of POSTAL SERVICE US ROANOKE in 419 RUTHERFORD AVE NE, ROANOKE, VA 24022 (NAICS 491110). OSHA activity number 334954393.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Postal Service US Roanoke for free Get an email when a new federal OSHA severe-injury report for Postal Service US Roanoke is published. One employer, no account, unsubscribe in one click.
Site address
419 RUTHERFORD AVE NE
City
ROANOKE
State
VA
ZIP
24022
Mailing
419 RUTHERFORD AVE NE, ROANOKE, VA 24022
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
491110
Employees
369
Ownership type
A

6 citations on file for this inspection.

1910.213 H04

Deleted Serious Gravity 5 1 instance 8 exposed
Issued
Jul 23, 2012
Penalty
Initial $3,400 · Current $0 Reduced
29 CFR 1910.213(h)(4):     Radial saw(s) were not installed in a manner so as to cause the cutting head to return gently to the starting position when released by the operator:    a.)   US Postal Service, Roanoke P&DC, Maintenance Shop, Craftsman 10inch radial arm saw, Serial No. 98280P0083, Model No. 113.196380, 3hp.  On or about June 19, 2012, the cutting head of the saw did not automatically return to its original starting position when released.
Recent events (2)
  • · I (S) $0
  • · Z (S) $3400

1910.304 G05

Other-than-serious 1 instance 2 exposed
Issued
Jul 23, 2012
Penalty
Initial $3,400 · Current $3,400
29 CFR 1910.304(g)(5):     The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:    a.)  US Postal Service, Roanoke P&DC, Consumer Affairs Office, Room 206.  On or about June 20, 2012, the wall mounted multi-receptacle (ten units) strip which was energized, and hard-wired to a 120v junction box was not grounded exposing employees to a potential shock hazard.
Recent events (2)
  • · I (O) $3400
  • · Z (S) $3400

1910.303 G01 II

Other-than-serious 1 instance 90 exposed
Issued
Jul 23, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii):     The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:    a.)  US Postal Service, Roanoke P&DC, Work Floor, Column C9, Electrical Panel LD6 120/208 volts, 3-phase.  On or about June 19, 2012, the area in front of the electrical panel was being used for storage in that plastic mail crates were stacked in front of the panel.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.303 B02

Other-than-serious 1 instance 2 exposed
Issued
Jul 23, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2):     Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:    a.)  US Postal Service, Roanoke P&DC, SMO's Office.  On or about June 19, 2012, an energized 3-way grounded male adapter plug was not used to its listed or labeled purpose in that it was used in lieu of permanent wiring by providing electrical service for a refrigerator and a microwave on a permanent basis.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.305 G02 III

Other-than-serious 1 instance 1 exposed
Issued
Jul 23, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii):     Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:    a.)  US Postal Service, Roanoke P&DC, East Dock near Contract Carrier Break Room #127.  On or about June 19, 2012, the Dayton 30" Pedestal Floor Fan, Model 4M197, did not have strain relief at the male attachment plug in that the outer insulating material was pulled away.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.305 G01 IV B

Other-than-serious 1 instance 17 exposed
Issued
Jul 23, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(B):     Flexible cords and cables were run through holes in walls, ceilings, or floors.    a.)  US Postal Service, Roanoke P&DC, IBSS Room.  On or about June 19, 2012, the flexible cords belonging to the four unit, 240v Siemen's Computer Mainframe(s) operating the mail processing and distribution equipment were partially hidden above the ceiling tiles where the male attachment plug were plugged into 240v junction boxes.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0