ST THOMAS, VI —
OSHA Inspection: BEST WESTERN EMERALD BEACH RESORT
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of BEST WESTERN EMERALD BEACH RESORT in 8070 LINDBERGH BAY, ST THOMAS, VI 00802 (NAICS 721110). OSHA activity number 334960606.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BEST WESTERN EMERALD BEACH RESORT
- Site address
- 8070 LINDBERGH BAY
- City
- ST THOMAS
- State
- VI
- ZIP
- 00802
- Mailing
- 8070 LINDBERGH BAY, ST THOMAS, VI 00802
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 721110
- Employees
- 77
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.303 F02
- Issued
- Sep 26, 2012
- Abate by
- Oct 18, 2012
- Penalty
- Initial $1,785 · Current $1,160 Reduced
General-duty citation text
29 CFR 1910.303(f)(2): Services, feeders, and branch circuits. Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident: On or about 06/28/12, at 8070 Lindbergh Bay, St Thomas, VI, in the laundry room area, the circuit breakers or fuses in the electrical service panel were not identified or labeled to show the locations of the building whose circuits it protects. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (2)
- — I (S) $1160.25
- — Z (S) $1785
1910.303 B02
- Issued
- Sep 26, 2012
- Abate by
- Oct 18, 2012
- Penalty
- Initial $1,785 · Current $1,160 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling: a) On or about 06/28/12, at 8070 Lindbergh Bay, St Thomas, VI, in the laundry room area, a relocatable power tap was not directly connected to a permanently installed branch circuit receptacle, and was connected to extension cords service portable electrical fans b) On or about 06/28/12, at 8070 Lindbergh Bay, St Thomas, VI, in the laundry room area, a relocatable power tap was connected to an extension cord to service portable electrical fans. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (2)
- — I (S) $1160.25
- — Z (S) $1785
1910.305 G01 IV A
- Issued
- Sep 26, 2012
- Abate by
- Oct 18, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used as a substitute for the fixed wiring of a structure: On or about 06/28/12, at 8070 Lindbergh Bay, St Thomas, VI, in the laundry room area, a relocatable power tap and flexible cords were used in lieu of permanent wiring to service portable electrical fans. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV C
- Issued
- Sep 26, 2012
- Abate by
- Oct 18, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(C): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used where run through doorways, windows, or similar openings: On or about 06/28/12, at 8070 Lindbergh Bay, St Thomas, VI, in the laundry room area, a flexible cords was run through a doorway to service portable electrical fans. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G01
- Issued
- Sep 26, 2012
- Penalty
- Initial $1,785 · Current $1,160 Reduced
General-duty citation text
29 CFR 1910.303(g)(1): Space about electric equipment. Sufficient access and working space shall be provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment: On or about 06/28/12, at 8070 Lindbergh Bay, St Thomas, VI, in the wine & spirits area, the electrical service panel was not readily accessible. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS NOT REQUIRED FOR THIS VIOLATION.
Recent events (2)
- — I (S) $1160.25
- — Z (S) $1785
1910.305 B01 II
- Issued
- Sep 26, 2012
- Abate by
- Oct 18, 2012
- Penalty
- Initial $1,785 · Current $1,160 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed: On or about 06/28/12, at 8070 Lindbergh Bay, St Thomas, VI, in the kitchen area, two circuit breaker panels had several unused openings not covered. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (2)
- — I (S) $1160.25
- — Z (S) $1785
More inspections at Best Western Emerald Beach Resort
View Best Western Emerald Beach Resort's full OSHA safety record →
More inspections in this industry (NAICS 721110)
More inspections in VI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 334960606.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.