OKANOGAN, WA ·
OSHA Inspection: OKANOGAN BINGO CASINO
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of OKANOGAN BINGO CASINO in 41 APPLE WAY ROAD, OKANOGAN, WA 98840 (NAICS 713210). OSHA activity number 335073789.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- OKANOGAN BINGO CASINO
- Site address
- 41 APPLE WAY ROAD
- City
- OKANOGAN
- State
- WA
- ZIP
- 98840
- Mailing
- 41 APPLE WAY ROAD, OKANOGAN, WA 98840
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 713210
- Employees
- 110
- Ownership type
- Private (A)
Citations
7 citations on file for this inspection.
1910.37 B02
- Issued
- Aug 20, 2012
- Abate by
- Sep 19, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit": a) Exit signs were not located over the exit discharge door in the Break Room Trailer and the Administrative Trailer, exposing employees to possible delayed egress hazards.
Recent events (1)
- · Z (O) $0
1910.303 B02
- Issued
- Aug 20, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) A toaster was plugged into a relocatable power tap in the Break Room, violating the power taps UL listing and labeling, exposing employees to potential electrical fire hazards.
Recent events (1)
- · Z (O) $0
1910.303 G01 II
- Issued
- Aug 20, 2012
- Abate by
- Sep 19, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): Working space for equipment likely to require examination, adjustment, servicing, or maintenance while energized was used for storage: a) Several beverage boxes were stored underneath the breaker panel in the Lounge Electrical Room, exposing employees to possible tripping hazards while trying to access the breaker panel.
Recent events (1)
- · Z (O) $0
1910.305 E01
- Issued
- Aug 20, 2012
- Abate by
- Sep 19, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in wet locations were not weatherproof: (a) The outside outlet used to power the Food Train was missing its weatherproof cover, exposing employees to possible electrical shock hazards.
Recent events (1)
- · Z (O) $0
1910.305 G01 IV A
- Issued
- Aug 20, 2012
- Abate by
- Sep 19, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and cables were used as a substitute for the fixed wiring of a structure: a) The Food Train has been powered by an extension cord for approximately 1-3 years, exposing employees to electrical shock hazards.
Recent events (1)
- · Z (O) $0
1910.305 J01 I
- Issued
- Aug 20, 2012
- Abate by
- Sep 19, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(1)(i): Fixtures, lampholders, lamps, rosettes, and receptacles located within 8 feet of the floor had live parts exposed to employee contact: a) The Lounge Electrical Room had an unguarded light bulb located 7 feet, 1 inch from the floor, exposing employees to possible electrical shock hazards, and broken glass. b) The Food Train had an unguarded light bulb located 7 feet 4 inches from the floor, exposing employees to possible electrical shock hazards and broken glass. c) The Beverage Outside Walk-In Trailer had an unguarded light bulb located 6 feet 6 inches from the floor, exposing employees to possible electrical shock hazards and broken glass. d) The Break Room Trailers Storage Room had an unguarded light bulb located 7 feet from the floor, exposing employees to possible electrical shock hazards and broken glass.
Recent events (1)
- · Z (O) $0
1910.333 B02 I
- Issued
- Aug 20, 2012
- Abate by
- Sep 19, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(b)(2)(i): The employer did not make a written copy of the procedures outlined in paragraph (b)(2) of 29 CFR 1910.333 available for inspection by employees and by the Assistant Secretary of Labor and his or her authorized representatives: a) The employer did not keep a copy of the Electrical Safe Workpractices standard for contractors and employees who perform maintenance on electrical equipment including but not limited to outlets, breaker panels, HVAC system, and air compressors. This is to prevent electrical shock hazards.
Recent events (1)
- · Z (O) $0
More inspections at Okanogan Bingo Casino
View Okanogan Bingo Casino's full OSHA safety record →
More inspections in this industry (NAICS 713210)
More inspections in WA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 335073789.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.