Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: BREDERO SHAW

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of BREDERO SHAW in 4501 KNAPP ROAD, PEARLAND, TX 77581 (NAICS 332996). OSHA activity number 335130787.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Bredero Shaw — free Get an email when a new federal OSHA severe-injury report for Bredero Shaw is published. One employer, no account, unsubscribe in one click.
Establishment
BREDERO SHAW
Site address
4501 KNAPP ROAD
City
PEARLAND
State
TX
ZIP
77581
Mailing
1122 NORTH MAIN STREET, PEARLAND, TX 77581
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332996
Employees
4322
Ownership type
A

2 citations on file for this inspection.

1910.157 C04

Other-than-serious 2 instances 1 exposed
Issued
Aug 27, 2012
Abate by
Sep 1, 2012
Penalty
Initial $4,000 · Current $2,800 Reduced
29 CFR 1910.157(c)(4):     Portable fire extinguishers were not kept in their designated places at all times except during use:    At the Bredero Shaw facility, located at 4501 Knapp Road, fire extinguishers were not stored in locations designated by signage. This was observed in the following instances;    a) Inside the Fusion Bond #1 building, North entrance, East wall and,    b) Inside the Fusion Bond #1 building, East most section, West wall.
Recent events (2)
  • — I (O) $2800
  • — Z (S) $4000

1910.303 G01 I A

Other-than-serious 1 instance 1 exposed
Issued
Aug 27, 2012
Abate by
Aug 28, 2012
Penalty
Initial $5,000 · Current $3,500 Reduced
29 CFR 1910.303(g)(1)(i)(A):     For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening whwere they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910:    In the Fusion Bond #1 facility, a service panel was blocked by a rack of housekeeping impliments, and the space availbale for work was approximately 16 inches, exposing maintenance employees to electrical hazards. According to Table S-1, at least three feet is required.