OSHA Inspection: MCDONALD ELECTRICAL CORPORATION

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of MCDONALD ELECTRICAL CORPORATION in 368 CONGRESS STREET, BOSTON, MA 02125 (NAICS 238210). OSHA activity number 335215182.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Mcdonald Electrical Corporation — free Get an email when a new federal OSHA severe-injury report for Mcdonald Electrical Corporation is published. One employer, no account, unsubscribe in one click.
Site address
368 CONGRESS STREET
City
BOSTON
State
MA
ZIP
02125
Mailing
72 SHARP STREET SUITE C-8, HINGHAM, MA 02043
Inspection type
Unprogrammed Other (I)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
40
Ownership type
A

2 citations on file for this inspection.

1926.403 I02 III

Deleted Serious Gravity 1 1 instance 3 exposed
Issued
Sep 13, 2012
Abate by
Sep 14, 2012
Penalty
Initial $1,785 · Current $0 Reduced
29 CFR 1926.403(i)(2)(iii): Entrances to rooms and other guarded locations containing exposed live parts operating at 600 volts, nominal, or less were not marked with conspicuous warning signs forbidding unqualified persons to enter:    (a) Location - 1st floor switchgear room (former boiler room) at 368 Congress Street, Boston:  An electrical room within the old bolier room, in which 480 volt equipment with live parts were located, did not have a sign on door indicating such room should only be entered by qualified persons.
Recent events (2)
  • — I (S) $0
  • — Z (S) $1785

1926.405 B01

Serious Gravity 5 2 instances 2 exposed
Issued
Sep 13, 2012
Abate by
Sep 18, 2012
Penalty
Initial $3,500 · Current $1,750 Reduced
29 CFR 1926.405(b)(1): Unused openings in cabinets, boxes, and fittings were not effectively closed:    (a) Location - 1st floor switchgear room (former boiler room) at 368 Congress Street, Boston:  On or about 06/28/12, the side of a live 120/208 vac electrical panel had several 1/2" romex connectors unused openings.    (b) Location - 1st floor switchgear room (former boiler room) at 368 Congress Street, Boston:  On or about 06/28/12, the 120/208 vac electrical panel had three breaker openings taped up, ineffectively blanked, to protect from live parts.