Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: BUDGET PRINTERS & EMBROIDERERS

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of BUDGET PRINTERS & EMBROIDERERS in 1718 PARK STREET, HARTFORD, CT 06106 (NAICS 323119). OSHA activity number 335237582.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Budget Printers & Embroiderers — free Get an email when a new federal OSHA severe-injury report for Budget Printers & Embroiderers is published. One employer, no account, unsubscribe in one click.
Site address
1718 PARK STREET
City
HARTFORD
State
CT
ZIP
06106
Mailing
1718 PARK STREET, HARTFORD, CT 06106
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
323119
Employees
24
Ownership type
A

7 citations on file for this inspection.

1910.304 A02

Serious Gravity 5 1 instance 24 exposed
Issued
Jan 22, 2013
Abate by
Mar 11, 2013
Penalty
Initial $1,360 · Current $792 Reduced
29 CFR 1910.304(a)(2):   Grounded conductors were attached to terminals or leads so as to reverse designated polarity:      Second Floor, Cafeteria:  On or about November 28, 2012, the 2-outlet receptacle powering a Black and Decker Toast R Oven showed reversed polarity.  Employees touching the metal parts of the equipment were exposed to electric shock hazards.
Recent events (2)
  • — I (S) $792
  • — Z (S) $1360

1910.304 G05

Serious Gravity 5 1 instance 24 exposed
Issued
Jan 22, 2013
Abate by
Mar 11, 2013
Penalty
Initial $1,360 · Current $816 Reduced
29 CFR 1910.304(g)(5):   The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:        Second Floor, Cafeteria:   On or about November 28, 2012, the 4-outlet receptacle into which the Emerson microwave oven, Model Number MW8998B was plugged had an open ground.  This condition exposed employees to electric shock hazards while touching the metal parts of the equipment.
Recent events (2)
  • — I (S) $816
  • — Z (S) $1360

1910.304 G06 VI C 8

Serious Gravity 5 1 instance 1 exposed
Issued
Jan 22, 2013
Abate by
Mar 11, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.304(g)(6)(vi)(C)(8): Exposed noncurrent-carrying metal parts of portable hand lamp that may become energized was not grounded:      Silkscreening Area:  On or about November 28, 2012, a two-wire clamp-on metal-encased lamp was not grounded.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B01 II

Serious Gravity 5 2 instances 24 exposed
Issued
Jan 22, 2013
Abate by
Mar 11, 2013
Penalty
Initial $1,360 · Current $816 Reduced
29 CFR 1910.305(b)(1)(ii):   Unused openings in boxes, cabinets, or fittings were not effectively closed:      On or about November 28, 2012, employees were exposed to electric shock hazards in the following areas:    A.  Embroidery Department:  An open knockout was observed on a 4-outlet electrical receptacle mounted on the wall at the front of the department, 16 inches from the ground.      B.  Plate Making Room:  Breakers/blanks were missing from the wall mounted 120V circuit breaker box.  An opening on the left side of the box measured 3/4" high x 2 1/2" wide 51 1/2" from the ground.  Another opening on the right of the box measured 1 1/2" high x 2 1/2" wide 48 1/2" from the ground.
Recent events (2)
  • — I (S) $816
  • — Z (S) $1360

1910.305 B02 I

Serious Gravity 5 2 instances 24 exposed
Issued
Jan 22, 2013
Abate by
Mar 11, 2013
Penalty
Initial $1,360 · Current $816 Reduced
29 CFR 1910.305(b)(2)(i):   Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:      On or about November 28, 2012, in the following locations, electrical receptacle boxes were missing faceplates, exposing employees to electrical shocks:    A.  Embroidery Department:  A single outlet electrical box mounted at the floor level in the front of the department was missing a faceplate.    B.  Silkscreen Area:  The electrical outlet mounted on the wall over the workbench was missing a faceplate.
Recent events (2)
  • — I (S) $816
  • — Z (S) $1360

1910.305 C04

Serious Gravity 5 1 instance 1 exposed
Issued
Jan 22, 2013
Abate by
Mar 11, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(c)(4):  Snap switches mounted in boxes did not have faceplates installed so as to completely cover the opening and seat against the finished surface:        Silkscreen Area:  A snap switch mounted on the wall above the work bench was not provided with a faceplate, exposing employees to electric shock hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B02

Other-than-serious 1 instance 1 exposed
Issued
Jan 22, 2013
Abate by
Mar 11, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2):   Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:        Silkscreen Area:  On or about November 28, 2012, a 4-outlet wall-mount listed electrical box with knockouts was installed against listing and labeling instructions to provide pendant power to the automatic press.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 335237582.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.