HARTFORD, CT —
OSHA Inspection: BUDGET PRINTERS & EMBROIDERERS
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of BUDGET PRINTERS & EMBROIDERERS in 1718 PARK STREET, HARTFORD, CT 06106 (NAICS 323119). OSHA activity number 335237582.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BUDGET PRINTERS & EMBROIDERERS
- Site address
- 1718 PARK STREET
- City
- HARTFORD
- State
- CT
- ZIP
- 06106
- Mailing
- 1718 PARK STREET, HARTFORD, CT 06106
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 323119
- Employees
- 24
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.304 A02
- Issued
- Jan 22, 2013
- Abate by
- Mar 11, 2013
- Penalty
- Initial $1,360 · Current $792 Reduced
General-duty citation text
29 CFR 1910.304(a)(2): Grounded conductors were attached to terminals or leads so as to reverse designated polarity: Second Floor, Cafeteria: On or about November 28, 2012, the 2-outlet receptacle powering a Black and Decker Toast R Oven showed reversed polarity. Employees touching the metal parts of the equipment were exposed to electric shock hazards.
Recent events (2)
- — I (S) $792
- — Z (S) $1360
1910.304 G05
- Issued
- Jan 22, 2013
- Abate by
- Mar 11, 2013
- Penalty
- Initial $1,360 · Current $816 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: Second Floor, Cafeteria: On or about November 28, 2012, the 4-outlet receptacle into which the Emerson microwave oven, Model Number MW8998B was plugged had an open ground. This condition exposed employees to electric shock hazards while touching the metal parts of the equipment.
Recent events (2)
- — I (S) $816
- — Z (S) $1360
1910.304 G06 VI C 8
- Issued
- Jan 22, 2013
- Abate by
- Mar 11, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(g)(6)(vi)(C)(8): Exposed noncurrent-carrying metal parts of portable hand lamp that may become energized was not grounded: Silkscreening Area: On or about November 28, 2012, a two-wire clamp-on metal-encased lamp was not grounded.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B01 II
- Issued
- Jan 22, 2013
- Abate by
- Mar 11, 2013
- Penalty
- Initial $1,360 · Current $816 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: On or about November 28, 2012, employees were exposed to electric shock hazards in the following areas: A. Embroidery Department: An open knockout was observed on a 4-outlet electrical receptacle mounted on the wall at the front of the department, 16 inches from the ground. B. Plate Making Room: Breakers/blanks were missing from the wall mounted 120V circuit breaker box. An opening on the left side of the box measured 3/4" high x 2 1/2" wide 51 1/2" from the ground. Another opening on the right of the box measured 1 1/2" high x 2 1/2" wide 48 1/2" from the ground.
Recent events (2)
- — I (S) $816
- — Z (S) $1360
1910.305 B02 I
- Issued
- Jan 22, 2013
- Abate by
- Mar 11, 2013
- Penalty
- Initial $1,360 · Current $816 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: On or about November 28, 2012, in the following locations, electrical receptacle boxes were missing faceplates, exposing employees to electrical shocks: A. Embroidery Department: A single outlet electrical box mounted at the floor level in the front of the department was missing a faceplate. B. Silkscreen Area: The electrical outlet mounted on the wall over the workbench was missing a faceplate.
Recent events (2)
- — I (S) $816
- — Z (S) $1360
1910.305 C04
- Issued
- Jan 22, 2013
- Abate by
- Mar 11, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(c)(4): Snap switches mounted in boxes did not have faceplates installed so as to completely cover the opening and seat against the finished surface: Silkscreen Area: A snap switch mounted on the wall above the work bench was not provided with a faceplate, exposing employees to electric shock hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 B02
- Issued
- Jan 22, 2013
- Abate by
- Mar 11, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: Silkscreen Area: On or about November 28, 2012, a 4-outlet wall-mount listed electrical box with knockouts was installed against listing and labeling instructions to provide pendant power to the automatic press.