Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: RUSSCO INC.

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of RUSSCO INC. in 306 HIAWATHA BLVD WEST DESTINY USA, SYRACUSE, NY 13204 (NAICS 236220). OSHA activity number 335301222.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Russco INC. — free Get an email when a new federal OSHA severe-injury report for Russco INC. is published. One employer, no account, unsubscribe in one click.
Establishment
RUSSCO INC.
Site address
306 HIAWATHA BLVD WEST DESTINY USA
City
SYRACUSE
State
NY
ZIP
13204
Mailing
565 COMMERCE DR. SUITE 2, FALL RIVER, MA 02720
Inspection type
Unprogrammed Related (G)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
236220
Employees
2
Ownership type
A

2 citations on file for this inspection.

1926.403 B02

Serious Gravity 5 2 instances 2 exposed
Issued
Oct 23, 2012
Abate by
Nov 6, 2012
Penalty
Initial $2,000 · Current $1,400 Reduced
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:    a) On or about 7/11/2012, Guess Store:  Card board was used to cover two energized circuit breaker boxes.    Abatement certification is required for this item.
Recent events (2)
  • — I (S) $1400
  • — Z (S) $2000

1926.404 B01 II

Serious Gravity 5 2 instances 2 exposed
Issued
Oct 23, 2012
Abate by
Nov 6, 2012
Penalty
Initial $1,600 · Current $1,120 Reduced
29 CFR 1926.404(b)(1)(ii): Ground-fault circuit interrupters. All 120-volt, single-phase 15- and 20-ampere receptacle outlets on construction sites, which are not a part of the permanent wiring of the building or structure and which are in use by employees, shall have approved ground-fault circuit interrupters for personnel protection. Receptacles on a two-wire, single-phase portable or vehicle-mounted generator rated not more than 5kW, where the circuit conductors of the generator are insulated from the generator frame and all other grounded surfaces, need not be protected with ground-fault circuit interrupters.    a) On or about 7/11/2012, Guess Store:  A DeWalt saw and a DeWalt drill were in use powered through extension cords without the use of a GFCI or assured equipment grounding program.    Abatement certification is required for this item.
Recent events (2)
  • — I (S) $1120
  • — Z (S) $1600

View Russco INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 335301222.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.