Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,197,549Inspections Most recent open 2026-08-27 Last loaded 2026-08-31

OSHA Inspection: ACCAD CORPORATION

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of ACCAD CORPORATION in ROUTE 219, MARLINTON, WV 24954 (NAICS 237310). OSHA activity number 335369583.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Accad Corporation for free Get an email when a new federal OSHA severe-injury report for Accad Corporation is published. One employer, no account, unsubscribe in one click.
Establishment
ACCAD CORPORATION
Site address
ROUTE 219
City
MARLINTON
State
WV
ZIP
24954
Mailing
865 CLINIC DRIVE, IVYDALE, WV 25113
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
237310
Employees
4
Ownership type
Private (A)

1 citation on file for this inspection.

1926.403 B02

Serious Gravity 5 2 instances 3 exposed
Issued
Oct 1, 2012
Abate by
Oct 9, 2012
Penalty
Initial $2,000 · Current $1,500 Reduced
29 CFR 1926.403(b)(2):      Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:    (a)Bridge Abutment #2:  The employer was using unprotected Type NM-B  (nonmetallic sheathed) cable to provide temporary power to the work site.  Approximately 200 feet of the NM-B cable was ran through trees and under an existing bridge to provide power to a Milwaukee circular saw and water pumps, as observed on July 23, 2012.    (b)Bridge Abutment #2:  The employer was using a 120 volt duplex electrical outlet box that was designed to be used as a mounted outlet box at the end of a NM cable to provide temporary power to the work site.  The outlet box was being used outdoors and not equipped with a cover to power a Milwaukee circular saw and water pumps, as observed on July 23, 2012.    Abatement Note: NFPA 70-National Electric Code (NEC) specifies locations where outlet boxes can be installed under Section 210.52-63.  NFPA 70-NEC specifies that NM cable shall be installed in dwellings and not permitted to be installed in wet locations under Section 334.10.     Abatement Certification Required for this Item.
Recent events (2)
  • · I (S) $1500
  • · Z (S) $2000

View Accad Corporation's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 335369583.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.