Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ANCHOR HOCKING

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of ANCHOR HOCKING in 1115 W. FIFTH STREET, LANCASTER, OH 43130 (NAICS 327212). OSHA activity number 335423638.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Anchor Hocking — free Get an email when a new federal OSHA severe-injury report for Anchor Hocking is published. One employer, no account, unsubscribe in one click.
Establishment
ANCHOR HOCKING
Site address
1115 W. FIFTH STREET
City
LANCASTER
State
OH
ZIP
43130
Mailing
1115 W. FIFTH STREET, LANCASTER, OH 43130
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
327212
Employees
1200
Ownership type
A

7 citations on file for this inspection.

1910.304 G05

Serious Gravity 5 10 instances 100 exposed
Issued
Oct 1, 2012
Abate by
Nov 14, 2012
Penalty
Initial $5,500 · Current $2,475 Reduced
29 CFR 1910.304(g)(5):     Grounding path. The path to ground from circuits, equipment, and enclosures shall be permanent, continuous, and effective.    A)  At the workplace, in the Set Packing Area, on line B1, an electrical fan did not have a continuous path to ground due to a missing grounding pin.    B)  At the workplace, in the Set Packing Area, on line C1, an electrical fan did not have a continuous path to ground due to a missing grounding pin.    C)  At the workplace, in the Set Packing Area, electrical label machine number 1 did not have a continuous path to ground due to a missing grounding pin.    D)  At the workplace, in the Set Packing Area, electrical label machine number 4 did not have a continuous path to ground due to a missing grounding pin.    E)  At the workplace, in the Set Packing Area, electrical label machine number 6 did not have a continuous path to ground due to a missing grounding pin.    F)  At the workplace, in the Set Packing Area, electrical label machine number 12 did not have a continuous path to ground due to a missing grounding pin.    G)  At the workplace, in the Set Packing Area, electrical label machine number 13 did not have a continuous path to ground due to a missing grounding pin.    H)  At the workplace, in the Set Packing Area, electrical label machine number 18 did not have a continuous path to ground due to a missing grounding pin.    I)  At the workplace, in the Set Packing Area, electrical label machine number 20 did not have a continuous path to ground due to a missing grounding pin.    J)  At the workplace, in the Set Packing Area, electrical label machine number 24 did not have a continuous path to ground due to a missing grounding pin.
Recent events (2)
  • — I (S) $2475
  • — Z (S) $5500

1910.305 B01 II

Serious Gravity 5 1 instance 100 exposed
Issued
Oct 1, 2012
Abate by
Nov 14, 2012
Penalty
Initial $5,500 · Current $2,475 Reduced
29 CFR 1910.305(b)(1)(ii):     Unused openings in cabinets, boxes, and fittings shall be effectively closed.    A)  At the workplace, in the Set Packing Area, on C1 Line, a junction box attached to an industrial fan had an approximately one inch opening exposing open wiring that was not effectively closed with a knockout plug.
Recent events (2)
  • — I (S) $2475
  • — Z (S) $5500

1910.305 B02 I

Serious Gravity 5 1 instance 100 exposed
Issued
Oct 1, 2012
Abate by
Nov 14, 2012
Penalty
Initial $5,500 · Current $2,475 Reduced
29 CFR 1910.305(b)(2)(i):     All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear.    A)  At the workplace, near lines F1 and F2 of the Set Pack Area, there was an electrical outlet mounted below the conveyor belt that did not have a properly installed faceplate to prevent employee exposure to contact with electrical current from exposed open wiring.
Recent events (2)
  • — I (S) $2475
  • — Z (S) $5500

1910.305 G01 I

Serious Gravity 5 8 instances 100 exposed
Issued
Oct 1, 2012
Abate by
Jan 15, 2013
Penalty
Initial $5,500 · Current $2,475 Reduced
29 CFR 1910.305(g)(1)(i):     Flexible cords and cables shall be approved for conditions of use and location.    A)  At the workplace, in the Set Pack Area, employees were using UPC labeling machine # 1 that was made in house by the employer which utilized a flexible cord.    B)  At the workplace, in the Set Pack Area, employees were using UPC labeling machine # 4 that was made in house by the employer which utilized a flexible cord.  The flexible cord was installed in the UPC label machine with a knot which created a fire hazard.    C)  At the workplace, in the Set Pack Area, employees were using UPC labeling machine # 6 that was made in house by the employer which utilized a flexible cord.      D)  At the workplace, in the Set Pack Area, employees were using UPC labeling machine # 12 that was made in house by the employer which utilized a flexible cord.     E)  At the workplace, in the Set Pack Area, employees were using UPC labeling machine # 13 that was made in house by the employer which utilized a flexible cord.      F)  At the workplace, in the Set Pack Area, employees were using UPC labeling machine # 18 that was made in house by the employer which utilized a flexible cord.      G)  At the workplace, in the Set Pack Area, employees were using UPC labeling machine # 20 that was made in house by the employer which utilized a flexible cord.  The flexible cord was installed in the UPC label machine with a knot which created a fire hazard.    J)  At the workplace, in the Set Pack Area, employees were using UPC labeling machine # 24 that was made in house by the employer which utilized a flexible cord.  The flexible cord was installed in the UPC label machine with a knot which created a fire hazard.
Recent events (2)
  • — I (S) $2475
  • — Z (S) $5500

1910.305 G01 IV A

Serious Gravity 5 2 instances 100 exposed
Issued
Oct 1, 2012
Abate by
Nov 14, 2012
Penalty
Initial $5,500 · Current $2,475 Reduced
29 CFR 1910.305(g)(1)(iv)(A):     Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used:  As a substitute for the fixed wiring of a structure;    A)  At the workplace, in the Set Packing Area,  on the C1 line, a black flexible cord rated for 220 VAC was used as a substitute for the fixed wiring of fans and conveyors.    B)  At the workplace, in the Set Packing Area,  on the C2 line, a black flexible cord rated for 220 VAC was used as a substitute for the fixed wiring of fans and conveyors.
Recent events (2)
  • — I (S) $2475
  • — Z (S) $5500

1910.305 G02 III

Serious Gravity 5 2 instances 100 exposed
Issued
Oct 1, 2012
Abate by
Nov 14, 2012
Penalty
Initial $5,500 · Current $2,475 Reduced
29 CFR 1910.305(g)(2)(iii):     Flexible cords and cables shall be connected to devices and fittings so that strain relief is provided that will prevent pull from being directly transmitted to joints or terminal screws.    A)  At the workplace, in the Set Packing Area, a retractable flexible cord mounted on the ceiling was not connected to a device and fitting so that strain relief was provided to the female end connector.    B)  At the workplace, in the Set Packing Area, a flexible cord connected to an industrial fan was not connected to a device and fitting so that strain relief was provided.
Recent events (2)
  • — I (S) $2475
  • — Z (S) $5500

1910.334 A02 II

Serious Gravity 5 1 instance 100 exposed
Issued
Oct 1, 2012
Abate by
Nov 14, 2012
Penalty
Initial $5,500 · Current $2,475 Reduced
29 CFR 1910.334(a)(2)(ii):     If there is a defect or evidence of damage that might expose an employee to injury, the defective or damaged item shall be removed from service, and no employee may use it until repairs and tests necessary to render the equipment safe have been made.    A)  At the workplace, in the Set Pack Area, on the C1 line, a four prong 220 volt outlet box had electrical tape holding the cover in place exposing employees to electrical hazards.
Recent events (2)
  • — I (S) $2475
  • — Z (S) $5500

View Anchor Hocking's full OSHA safety record →