LEWISTON, ID ·
OSHA Inspection: LES SCHWAB TIRE CENTERS OF IDAHO, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of LES SCHWAB TIRE CENTERS OF IDAHO, INC. in 1408 MAIN STREET, LEWISTON, ID 83501 (NAICS 423130). OSHA activity number 335461182.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- LES SCHWAB TIRE CENTERS OF IDAHO, INC.
- Site address
- 1408 MAIN STREET
- City
- LEWISTON
- State
- ID
- ZIP
- 83501
- Mailing
- POB 716, LEWISTON, ID 83501
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 423130
- Employees
- 24
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.213 A09
- Issued
- Dec 12, 2012
- Abate by
- Dec 18, 2012
- Penalty
- Initial $2,250 · Current $2,250
General-duty citation text
29 CFR 1910.213(a)(9): All belts, pulleys, gears, shafts, and moving parts were not guarded in accordance with the specific requirements of 1910.219 (a) Back of the main shop: On or about July 10, 2012, and at times prior thereto, the belt and pulley on a squirrel cage fan, model PQD56S17D2048E had the belt and pulley exposed. (b) Back of the main shop: On or about July 10, 2012, and at times prior thereto, the belt and pulley on a squirrel cage fan, model SX5000 had the belt and pulley exposed. Note: Abatement certification IS required for this item.
Recent events (1)
- · Z (S) $2250
1910.305 B01 I
- Issued
- Dec 12, 2012
- Abate by
- Dec 24, 2012
- Penalty
- Initial $2,250 · Current $2,250
General-duty citation text
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions: (a) Truck Shop Bathroom: On or about July 10, 2012 and at times prior thereto, two exposed hot conductors were not protected with a cover. (a) Advanced Building: On or about July 10, 2012 and at times prior thereto, exposed hot conductor on the switch box was not protected with a cover. Note: Abatement certification IS required for this item.
Recent events (1)
- · Z (S) $2250
1910.305 B01 II
- Issued
- Dec 12, 2012
- Abate by
- Dec 24, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: (a) Advanced Building: On or about July 10, 2012, and at times prior thereto, A switch box had three (3) knockouts missing exposing the internal conductors. (b) Outside of the truck stop bathroom: On or about July 10, 2012, and at times prior thereto, the electrical panel box was in need of a cover for a vacant circuit breaker space. Abatement certification IS required for this item.
Recent events (1)
- · Z (S) $0
1910.303 G01 II
- Issued
- Dec 12, 2012
- Abate by
- Dec 24, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: (a) Advanced Building: On or about July 10, 2012, and at times prior thereto, tires and excess equipment were being stored in front of the electrical breaker panels. Note: Abatement certification IS required for this item.
Recent events (1)
- · Z (S) $0
1910.305 G02 III
- Issued
- Dec 12, 2012
- Abate by
- Dec 24, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: (a) New addition: On or about July 10, 2012, and at times prior thereto, the Lester Electrical Charging Unit, model 17930, serial 02-00 electrical cord was in need of strain relief. (b) Bay area: On or about July 10, 2012, the squirrel cage fan, model PQD56S17D2048E electrical cord was in need of strain relief. Note: Abatement certification IS required for this item.
Recent events (1)
- · Z (S) $0
1910.157 E02
- Issued
- Dec 12, 2012
- Abate by
- Dec 18, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly: (a) On or about July 10, 2012, and at times prior thereto, portable fire extinguishers were located throughout the workplace and had not received visual checks to ensure they were charged and ready for use in the event of a fire. Note: Abatement certification IS required for this item.
Recent events (1)
- · Z (O) $0
More inspections in this industry (NAICS 423130)
More inspections in ID
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 335461182.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.