On , OSHA opened a programmed Related safety inspection of U.S. ARMY CORPS OF ENGINEERS - LOS ANGELES DISTRICT in 915 WILSHIRE BLVD. STE 1525, LOS ANGELES, CA 90017 (NAICS 541330). OSHA activity number 335638383.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U.S. ARMY CORPS OF ENGINEERS - LOS ANGELES DISTRICT
- Site address
- 915 WILSHIRE BLVD. STE 1525
- City
- LOS ANGELES
- State
- CA
- ZIP
- 90017
- Mailing
- 915 WILSHIRE BLVD. STE 1525, LOS ANGELES, CA 90017
What kind of inspection was it?
- Inspection type
- Programmed Related (I)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 541330
- Employees
- 400
- Ownership type
- Federal government (D)
Citations
4 citations on file for this inspection.
1910.303 B02
- Issued
- Aug 21, 2012
- Abate by
- Sep 12, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling. (a) 13th floor file storage area: On or about 2AUG12 at 0959hrs, a relocatable power tap was used to provide 115VAC service to a microwave and coffee pot. (b) 13th floor hallway outside cubicle 13043: On or about 2AUG12 at 1015hrs, a relocatable power tap was used to provide 115VAC service to a microwave and toaster. (c) 13th floor break area: On or about 2AUG12 at 1030hrs, a relocatable power tap was used to provide 115VAC service to a microwave, toaster oven and coffee pot. (d) 11th floor supply and safety cubicle: On or about 2AUG12 at 1102hrs, a relocatable power tap was used to provide 115VAC service to a coffee pot. (e) 11th floor supply and safety cubicle: On or about 2AUG12 at 1102hrs, a relocatable power tap was used to provide 115VAC service to a microwave oven and fluorescent light fixture.
Recent events (1)
- · Z (S) $0
1910.303 G02 I
- Issued
- Aug 21, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): (a) 11th floor cubicle adjacent to 11075: On or about 2AUG12 at 1126hrs, a relocatable power tap was used with exposed live parts to provide 115VAC service to a computer monitor.
Recent events (1)
- · Z (S) $0
1910.305 G01 IV A
- Issued
- Aug 21, 2012
- Abate by
- Sep 12, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and cables were used as a substitute for the fixed wiring of a structure (a) 13th floor chief of engineering office: On or about 2AUG12 at 1004hrs, a flexible cord set was used to provide 115VAC service to a refrigerator, microwave oven and toaster in lieu of the fixed wiring of the structure. (b) 13th floor cubicle 13041: On or about 2AUG12 at 1012hrs, a flexible cord set was used to provide 115VAC service to a refrigerator in lieu of the fixed wiring of the structure. (c) 11th hallway near cubicle 11077: On or about 2AUG12 at 1113hrs, a flexible cord set was used to provide 115VAC service to a microwave oven and toaster in lieu of the fixed wiring of the structure.
Recent events (1)
- · Z (S) $0
1910.305 G01 IV D
- Issued
- Aug 21, 2012
- Abate by
- Sep 12, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables were attached to building surfaces: (a) 13th floor break area: On or about 2AUG12 at 1030hrs, a relocatable power tap was affixed to the wall of a break room cabinet in order to provide 115VAC service to small kitchen appliances on the cabinet.
Recent events (1)
- · Z (S) $0
More inspections in this industry (NAICS 541330)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 335638383.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.