FALL RIVER, MA ·
OSHA Inspection: CELLULAR SALES OF MASSACHUSETTS, LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of CELLULAR SALES OF MASSACHUSETTS, LLC in 465 WILLIAM S. CANNING BLVD, FALL RIVER, MA 02721 (NAICS 443112). OSHA activity number 335693388.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CELLULAR SALES OF MASSACHUSETTS, LLC
- Site address
- 465 WILLIAM S. CANNING BLVD
- City
- FALL RIVER
- State
- MA
- ZIP
- 02721
- Mailing
- 25 LAFAYETTE ROAD, NORTH HAMPTON, NH 03862
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 443112
- Employees
- 4
- Ownership type
- A
Citations
11 citations on file for this inspection.
1910.38 A
- Issued
- Dec 26, 2012
- Abate by
- Feb 28, 2013
- Penalty
- Initial $2,800 · Current $1,400 Reduced
General-duty citation text
29 CFR 1910.38(a): The employer did not establish a written emergency evacuation plan for employees expected to evacuate in the event of a fire or other emergency. Location - 465 William S. Canning Blvd, Fall River, MA: On or about 07/10/12, the employer did not implement or orally communicate an emergency action plan for employees working at the Fall River store.
Recent events (2)
- · I (S) $1400
- · Z (S) $2800
1910.39 B
- Issued
- Dec 26, 2012
- Abate by
- Feb 28, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.39(b): Written and oral fire prevention plans. A fire prevention plan must be in writing, be kept in the workplace, and be made available to employees for review. However, an employer with 10 or fewer employees may communicate the plan orally to employees. Location - 465 William S. Canning Blvd, Fall River, MA: On or about 07/10/12, the employer did not communicate orally a fire prevention plan.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.141 C01 I
- Issued
- Dec 26, 2012
- Abate by
- Jan 4, 2013
- Penalty
- Initial $2,100 · Current $1,050 Reduced
General-duty citation text
29 CFR 1910.141(c)(1)(i): Separate toilet rooms for each sex were not provided where toilet rooms would be occupied by no more than one person at a time, and could not be locked from the inside. Location - 465 William S. Canning Blvd, Fall River, MA; Clerk desk area: On or about 07/10/12, the single occupancy toilet room door did not latch properly.
Recent events (2)
- · I (S) $1050
- · Z (S) $2100
1910.303 B02
- Issued
- Dec 26, 2012
- Abate by
- Jan 2, 2013
- Penalty
- Initial $2,800 · Current $1,400 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: Location - 465 William S. Canning Blvd, Fall River, MA: On or about 07/10/12, the following equipment at the cell phone retail store, was not being used in accordance to its listing and lableing: Instance a: a two prong extention cord was being used with equipment requiring a 3 prong grounded cord. Instance b: a relocatable power tap was used in conjuction with a extension cord. Instance c: a microvawe oven was not plugged directly into a grounded receptacle.
Recent events (2)
- · I (S) $1400
- · Z (S) $2800
1910.304 B02
- Issued
- Dec 26, 2012
- Abate by
- Jan 2, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(b)(2): Outlet devices had an ampere rating less than the load being served. Location - 465 William S. Canning Blvd, Fall River, MA: On or about 07/10/12, a light weight extention cord was used in conjunction with a three prong to two prong adapter for providing power to a Relocatable Power Tap and a microwave oven potentially overloading the cord/outlet device.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.304 G05
- Issued
- Dec 26, 2012
- Abate by
- Jan 2, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(g)(5): The paths to ground from circuits, equipment, and enclosures were not permanent, continuous, and effective. Location - 465 William S. Canning Blvd, Fall River, MA: On or about 07/10/12, a two prong extention cord was used in conjunction with a three prong to two prong adapter for providing power to a Relocatable Power Tap and a microwave oven.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.303 G01
- Issued
- Dec 26, 2012
- Abate by
- Jan 25, 2013
- Penalty
- Initial $2,800 · Current $1,400 Reduced
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: Location - 465 William S. Canning Blvd, Fall River, MA: On or about 07/10/12, a retail sales counter with a desktop computer monitor screen and keyboard was installed in front of the main electrical panel.
Recent events (2)
- · I (S) $1400
- · Z (S) $2800
1910.305 B02 I
- Issued
- Dec 26, 2012
- Abate by
- Jan 4, 2013
- Penalty
- Initial $3,500 · Current $1,750 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: Location - 465 William S. Canning Blvd, Fall River, MA: On or about 07/10/12, a two-gang receptacle wall outlet did not have a cover plate exposing employees to live conductors and live side terminal screws.
Recent events (2)
- · I (S) $1750
- · Z (S) $3500
1910.305 J01 I
- Issued
- Dec 26, 2012
- Abate by
- Jan 2, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(1)(i): Fixtures, lampholders, lamps, rosettes, and receptacles may have no live parts normally exposed to employee contact. However, rosettes and cleat-type lampholders and receptacles located at least 2.44 m (8.0 ft) above the floor may have exposed terminals. Location - 465 William S. Canning Blvd, Fall River, MA: On or about 07/10/12, a two-gang receptacle wall outlet was not secured to the rough in box exposing employees to live terminals on the sides of each receptacle.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.305 G01 IV A
- Issued
- Dec 26, 2012
- Abate by
- Jan 25, 2013
- Penalty
- Initial $2,800 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and cables were used as a substitute for the fixed wiring of a structure. Location - 465 William S. Canning Blvd, Fall River, MA; Washroom: On or about 07/10/12, extensions cord were used in lieu of fixed wiring. Instance a: a two prong cord was run along the floor and walls in toilet room to supply an RPT. Instance b: an extension cord was run through a ceiling to supply power to a DVD player.
Recent events (2)
- · I (S) $0
- · Z (S) $2800
1910.305 G01 IV B
- Issued
- Dec 26, 2012
- Abate by
- Jan 25, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and cables were run through holes in walls, ceilings, or floors. Location - 465 William S. Canning Blvd, Fall River, MA; Clerk desk area: On or about 07/10/12, An extension cord was run through a ceiling and used to power a DVD player.
Recent events (2)
- · I (S) $0
- · Z (S) $0
More inspections in this industry (NAICS 443112)
More inspections in MA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 335693388.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.