NEWHALEM, WA —
OSHA Inspection: NATIONAL PARK SERVICE NORTH CASCADES, NEWHALEM CAMP TENDER
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of NATIONAL PARK SERVICE NORTH CASCADES, NEWHALEM CAMP TENDER in STATE ROUTE 20, NEWHALEM, WA 98283 (NAICS 712190). OSHA activity number 335740007.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Site address
- STATE ROUTE 20
- City
- NEWHALEM
- State
- WA
- ZIP
- 98283
- Mailing
- 810 STATE ROUTE 20, SEDRO WOOLLEY, WA 98284
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 712190
- Employees
- 1
- Ownership type
- D
Citations
4 citations on file for this inspection.
1910.303 B02
- Issued
- Aug 30, 2012
- Abate by
- Oct 15, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing or labeling: a) Tender Room, where an orange extension cord and a relocatable power tap were daisy chained and used to supply power to the telephone located in the communication cabinet.
Recent events (1)
- — Z (O) $0
1910.305 G01 IV A
- Issued
- Aug 30, 2012
- Abate by
- Oct 15, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used as a substitute for the fixed wiring of a structure: a) Tender Room, where an orange extension cord was used to supply power to a relocatable power tap and the telephone located in the communication cabinet.
Recent events (1)
- — Z (O) $0
1910.303 G01 II
- Issued
- Aug 30, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
1910.303(g)(1)(ii): Working space for equipment likely to require examination, adjustment, servicing, or maintenance while energized was used for storage: a) Tender Room, where items including a desk and chairs were stored in front of circuit panels M and N.
Recent events (1)
- — Z (O) $0
1910.305 J01 I
- Issued
- Aug 30, 2012
- Abate by
- Oct 15, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29CFR1910.305(j)(1)(i): Fixtures, lampholders, lamps, rosettes, and receptacles may have no live parts normally exposed to employee contact. However, rosettes and cleat-type lampholders and receptacles located at least 2.44 m (8.0 ft) above the floor may have exposed terminals: a) Tender Room, where the light fixtures located 7 feet 6 inches above floor level were equipped with unguarded single bulbs.
Recent events (1)
- — Z (O) $0
More inspections at National Park Service North Cascades, Newhalem Camp Tender
View National Park Service North Cascades, Newhalem Camp Tender's full OSHA safety record →
More inspections in this industry (NAICS 712190)
More inspections in WA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 335740007.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.