BROKEN BOW, NE —
OSHA Inspection: GOLDEN LIVING CENTER - BROKEN BOW
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of GOLDEN LIVING CENTER - BROKEN BOW in 224 SO. E ST., BROKEN BOW, NE 68822 (NAICS 623110). OSHA activity number 335789582.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- GOLDEN LIVING CENTER - BROKEN BOW
- Site address
- 224 SO. E ST.
- City
- BROKEN BOW
- State
- NE
- ZIP
- 68822
- Mailing
- 224 SO. E ST., BROKEN BOW, NE 68822
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 623110
- Employees
- 57
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.303 G01
- Issued
- Nov 16, 2012
- Penalty
- Initial $3,179 · Current $2,225 Reduced
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment. Access to three (3) electrical circuit breaker panels, labled A5, M, and N, located in a facility storage room, was completely blocked by stored equipment.
Recent events (2)
- — I (S) $2225.3
- — Z (S) $3179
1910.332 B01
- Issued
- Nov 16, 2012
- Abate by
- Jan 31, 2013
- Penalty
- Initial $4,675 · Current $3,273 Reduced
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments. Maintenance employee had not received required safety training before performing electrical work including, but not limited to dining room fluorescent light ballast change and resident room duplex outlet replacement.
Recent events (2)
- — I (S) $3272.5
- — Z (S) $4675
1910.333 B02
- Issued
- Nov 16, 2012
- Abate by
- Jan 7, 2013
- Penalty
- Initial $4,675 · Current $3,273 Reduced
General-duty citation text
29 CFR 1910.333(b)(2): While an employee was exposed to contact with parts of fixed electric equipment or circuits which were deenergized, the circuits energizing the parts were not locked out or tagged or both in accordance with the requirements of this paragraph (b) of 29 CFR 1910.333(b)(2). Lockout devices were not used by employee(s) before performing electrical work including, but not limited to dining room fluorescent light ballast change and resident room duplex outlet replacement.
Recent events (2)
- — I (S) $3272.5
- — Z (S) $4675
More inspections in this industry (NAICS 623110)