OSHA Inspection: NATIONAL PARK SERVICE - CABRILLO NATIONAL MONUMENT

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of NATIONAL PARK SERVICE - CABRILLO NATIONAL MONUMENT in 1800 CABRILLO MEMORIAL DRIVE, SAN DIEGO, CA 92106 (NAICS 712190). OSHA activity number 335856043.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch National Park Service - Cabrillo National Monument — free Get an email when a new federal OSHA severe-injury report for National Park Service - Cabrillo National Monument is published. One employer, no account, unsubscribe in one click.
Site address
1800 CABRILLO MEMORIAL DRIVE
City
SAN DIEGO
State
CA
ZIP
92106
Mailing
1800 CABRILLO MEMORIAL DRIVE, SAN DIEGO, CA 92106
Inspection type
Unprogrammed Other (I)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
712190
Employees
125
Ownership type
D

12 citations on file for this inspection.

1910.37 A03

Serious Gravity 1 1 instance 4 exposed
Issued
Oct 5, 2012
Abate by
Oct 18, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed:    Maintenance Building: On or about 20AUG12, 1516hrs, a large pedestal fan was placed in the exit route.
Recent events (1)
  • — Z (S) $0

1910.212 A01

Serious Gravity 1 1 instance 3 exposed
Issued
Oct 5, 2012
Abate by
Oct 18, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:    Maintenance Building: On or about 20AUG12, 1454hrs, the drill press lacked a method of machine guarding to protect employees from flying chips and sparks.
Recent events (1)
  • — Z (S) $0

1910.213 H01

Serious Gravity 5 1 instance 3 exposed
Issued
Oct 5, 2012
Abate by
Oct 18, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.213(h)(1): The upper hood shall completely enclose the upper portion of the blade down to a point that will include the end of the saw arbor. The upper hood shall be constructed in such a manner and of such material that it will protect the operator from flying splinters, broken saw teeth, etc., and will deflect sawdust away from the operator. The sides of the lower exposed portion of the blade shall be guarded to the full diameter of the blade by a device that will automatically adjust itself to the thickness of the stock and remain in contact with stock being cut to give maximum protection possible for the operation being performed.    Maintenance Building: On or about 20AUG12, 1456hrs, the blade guard on a radial arm saw was adjusted to remain fixed in the upper position exposing employees using the saw to injury from the rotating saw blade.
Recent events (1)
  • — Z (S) $0

1910.215 B09

Serious Gravity 5 1 instance 3 exposed
Issued
Oct 5, 2012
Abate by
Oct 18, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.215(b)(9): Exposure adjustment. Safety guards of the types described in Subparagraphs (3) and (4) of this paragraph, where the operator stands in front of the opening, shall be constructed so that the peripheral protecting member can be adjusted to the constantly decreasing diameter of the wheel. The maximum angular exposure above the horizontal plane of the wheel spindle as specified in paragraphs (b)(3) and (4) of this section shall never be exceeded, and the distance between the wheel periphery and the adjustable tongue or the end of the peripheral member at the top shall never exceed one-fourth inch. (See Figures O-18, O-19, O-20, O-21, O-22, and O-23.)    Maintenance Building: On or about 20AUG12, 1434hrs, the tongue guard was not adjusted to within on quarter inch of the grinding wheel surface when used by the employees.
Recent events (1)
  • — Z (S) $0

1910.215 D03

Serious Gravity 5 1 instance 3 exposed
Issued
Oct 5, 2012
Abate by
Oct 18, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.215(d)(3): Surface condition. All contact surfaces of wheels, blotters and flanges shall be flat and free of foreign matter.    Maintenance Building: On or about 20AUG12, 1434hrs, aluminum residue coated surfaces of the grinding wheel.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Serious Gravity 5 3 instances 15 exposed
Issued
Oct 5, 2012
Abate by
Oct 18, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:    (a) Law Enforcement Offices:  On or about 20AUG12, 1254 hours, a surge suppressor was used to provide 15VAC electrical service to a coffee pot.    (b) Kitchen:  On or about 20AUG12, 1302 hours, a surge suppressor was used to provide 15VAC electrical service to a toaster and microwave oven.    (c) Library:  On or about 20AUG12, 1316 hours, a surge suppressor was used to provide 15VAC electrical service to a pedestal fan.
Recent events (1)
  • — Z (S) $0

1910.303 G01 I A

Serious Gravity 5 1 instance 5 exposed
Issued
Oct 5, 2012
Abate by
Oct 18, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening whwere they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910:    Kitchen:  On or about 20AUG12, 1306 hours, a large piece of furniture was placed in front of the circuit breaker panel access door inside the 30 inch keep clear zone marked on the floor in front of the panel.
Recent events (1)
  • — Z (S) $0

1910.305 A04 III

Serious Gravity 5 1 instance 1 exposed
Issued
Oct 5, 2012
Abate by
Oct 18, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(a)(4)(iii): The flexible nonmetallic tubing in which conductors were enclosed was not in continuous lengths of 15 feet or less:    Resources Field Office: On or about 20AUG12, 1324hrs, conductors in the plastic tubing were exposed where the tubing was removed to place a metal bracing across the conductors path.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV C

Serious Gravity 1 1 instance 4 exposed
Issued
Oct 5, 2012
Abate by
Oct 18, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(C): Flexible cords and cables were run through doorways, windows, or similar openings:    Maintenance Building: On or about 20AUG12, 1516hrs, a flexible cord was run through a door opening.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV D

Serious Gravity 5 2 instances 15 exposed
Issued
Oct 5, 2012
Abate by
Oct 18, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables were attached to building surfaces.    (a) Kitchen: On or about 20AUG12, 1306 hours, a surge suppressor was attached to the wall.    (b) Maintenance Building: On or about 20AUG12, 1503 hours, a surge suppressor was attached to the wall.
Recent events (1)
  • — Z (S) $0

1910.305 G02 III

Serious Gravity 1 1 instance 3 exposed
Issued
Oct 5, 2012
Abate by
Oct 18, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:    Maintenance Building: On or about 20AUG12, 1444hrs, the strain relief of the electrical connection cord on the compound miter saw was dry rotted at the base exposing the connectors.
Recent events (1)
  • — Z (S) $0

1910.1200 G08

Serious Gravity 5 1 instance 4 exposed
Issued
Oct 5, 2012
Abate by
Oct 18, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.12009g)(8): The employer shall maintain in the workplace copies of the required material safety data sheets for each hazardous chemical, and shall ensure that they are readily accessible during each work shift to employees when they are in their work area(s). (Electronic access, microfiche, and other alternatives to maintaining paper copies of the material safety data sheets are permitted as long as no barriers to immediate employee access in each workplace are created by such options.)    Maintenance Building: On or about 20AUG12, 1406hrs, The employer did not maintain MSDS for Butcher's baseboard and buildup stripper and Robert's universal carpet seam sealer chemicals provided in the workplace, the chemicals were identified as items normally used by the employees.
Recent events (1)
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 335856043.