LAUREL, MT —
OSHA Inspection: COLLECTIVE RECYCLERS & SERVICES
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of COLLECTIVE RECYCLERS & SERVICES in 1315 ALLENDALE ROAD, LAUREL, MT 59044 (NAICS 562920). OSHA activity number 335915385.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- COLLECTIVE RECYCLERS & SERVICES
- Site address
- 1315 ALLENDALE ROAD
- City
- LAUREL
- State
- MT
- ZIP
- 59044
- Mailing
- 1315 ALLENDALE ROAD, LAUREL, MT 59044
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 562920
- Employees
- 7
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.303 B01
- Issued
- Jan 31, 2013
- Abate by
- May 10, 2013
- Penalty
- Initial $1,600 · Current $960 Reduced
General-duty citation text
29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees: (a) South side of building: On or about August 24, 2012 and at times prior thereto, employees were exposed to shock hazards due to an outlet and light switch with components extending out of their electrical boxes.
Recent events (3)
- — F (S) $960
- — C (S) $1600
- — Z (S) $1600
1910.305 B02
- Issued
- Jan 31, 2013
- Abate by
- May 10, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: (a) South end of Collective Recyclers & Services: On or about August 24, 2012 and at times prior thereto, employees were exposed to shock/fire hazards from junction boxes, outlets and switches that were not provided appropriate covers.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.303 G01
- Issued
- Jan 31, 2013
- Abate by
- May 10, 2013
- Penalty
- Initial $1,600 · Current $960 Reduced
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: (a) Collective Recyclers & Services: On or about August 24, 2012 and at times prior thereto, employees were exposed to electrical shock hazards in the event that the circuit disconnect panel had to be accessed due to a pallet jack and grocery cart blocking the working space in front of the panel.
Recent events (3)
- — F (S) $960
- — C (S) $1600
- — Z (S) $1600
1910.303 G02 I
- Issued
- Jan 31, 2013
- Abate by
- May 10, 2013
- Penalty
- Initial $2,800 · Current $1,680 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): (a) Collective Recyclers & Services: On or about August 24, 2012 and at times prior thereto, employees were exposed to electrical shock hazards due to a sheet of plywood used to guard the electrical panel.
Recent events (3)
- — F (S) $1680
- — C (S) $2800
- — Z (S) $2800
1910.305 G01 IV B
- Issued
- Jan 31, 2013
- Abate by
- May 10, 2013
- Penalty
- Initial $1,600 · Current $960 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(B): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used: Where run through holes in walls, ceilings, or floors: (a) Baling area of building: Employees exposed to the hazard of electrical shock due to a flexible electrical cord run through a hole in the wall.
Recent events (3)
- — F (S) $960
- — C (S) $1600
- — Z (S) $1600
1910.37 B02
- Issued
- Jan 31, 2013
- Abate by
- May 10, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit": (a) South side of building: Employees exposed to hazards such as but not limited to tripping, falling, or not being able to recognize the exit in an emergency.
Recent events (3)
- — F (O) $0
- — C (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 562920)
More inspections in MT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 335915385.