SAN MARCOS, CA —
OSHA Inspection: NORTHROP GRUMMAN
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of NORTHROP GRUMMAN in 727 W SAN MARCOS BLVD STE 101-103, SAN MARCOS, CA 92078 (NAICS 928110). OSHA activity number 335943585.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NORTHROP GRUMMAN
- Site address
- 727 W SAN MARCOS BLVD STE 101-103
- City
- SAN MARCOS
- State
- CA
- ZIP
- 92078
- Mailing
- 727 W SAN MARCOS BLVD STE 101-103, SAN MARCOS, CA 92078
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 928110
- Employees
- 6
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.303 G01 I A
- Issued
- Oct 19, 2012
- Abate by
- Oct 30, 2012
- Penalty
- Initial $3,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening whwere they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910: The employer did not ensure accessability to the electrical pannel located in the far left corner in the office supply storage room and near employee bathroom as it was blocked with material.
Recent events (2)
- — I (S) $0
- — Z (S) $3000
1910.304 B03 I
- Issued
- Oct 19, 2012
- Abate by
- Nov 15, 2012
- Penalty
- Initial $3,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.304(b)(3)(i): All 125-volt, single-phase, 15- and 20-ampere receptacles installed in bathrooms or on rooftops shall have ground-fault circuit-interrupter protection for personnel. Employer did not ensure that employee bathroom was protected with ground fault circuit interrupter protection (GFCI). This was observed on 24 August 2012 in the employee restroom located on the northeast side of building that had a receptacle within 3 ft of a sink that was not protected by GFCI.
Recent events (2)
- — I (S) $0
- — Z (S) $3000
1910.305 G02 III
- Issued
- Oct 19, 2012
- Abate by
- Nov 2, 2012
- Penalty
- Initial $3,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: Strain relief was not provided on the cord to the shredder. The insullation had seperated from the plug and exposing the conductor. This was observed on or about 24 August 2012.
Recent events (2)
- — I (S) $0
- — Z (S) $3000
More inspections at Northrop Grumman
View Northrop Grumman's full OSHA safety record →
More inspections in this industry (NAICS 928110)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 335943585.