OSHA Inspection: L & B ELECTRICAL INTERNATIONAL, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of L & B ELECTRICAL INTERNATIONAL, INC. in 3007 FARRAGUT ROAD, BROOKLYN, NY 11210 (NAICS 238210). OSHA activity number 336126388.

Watch L & B Electrical International, INC. — free Get an email when a new federal OSHA severe-injury report for L & B Electrical International, INC. is published. One employer, no account, unsubscribe in one click.
Site address
3007 FARRAGUT ROAD
City
BROOKLYN
State
NY
ZIP
11210
Mailing
2063 ATLANTIC AVE., BROOKLYN, NY 11233
Inspection type
Referral (C)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
2
Ownership type
A

2 citations on file for this inspection.

1926.405 A02 II E

Serious Gravity 5 1 instance 2 exposed
Issued
Penalty
Initial $2000.00 · Current $1250.00 Reduced
29 CFR 1926.405(a)(2)(ii)(E): Lamps used in temporary wiring for general illumination were not protected from accidental contact or breakage.    a) Basement, north side:    Two employees were working on two electrical panels, and were using two light bulbs for general illumination and the light bulbs were not protected from accidental contact or breakage. On or about 08/30/12.    Note:  Because abatement of this violation is already documented in the inspection case file, the employer need not submit certification of abatement for this violation as normally required by 29 CFR 1903.19.
Recent events (2)
  • — I (S) $1250
  • — Z (S) $2000

1926.416 A01

Serious Gravity 10 1 instance 2 exposed
Issued
Penalty
Initial $2800.00 · Current $1500.00 Reduced
29 CFR 1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means.    a) Basement, north side:    Two employees were installing circuit breakers onto two energized 480V electrical panels. Employees were not protected against electric shock by de-energizing the panels, or wearing personal protective equipment. On or about 08/30/12.    Note:  Because abatement of this violation is already documented in the inspection case file, the employer need not submit certification of abatement for this violation as normally required by 29 CFR 1903.19.
Recent events (2)
  • — I (S) $1500
  • — Z (S) $2800