Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: MULLEN ELECTRIC CO.

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of MULLEN ELECTRIC CO. in 1670 KOHLER'S CROSSING, KYLE, TX 78640 (NAICS 238210). OSHA activity number 336143193.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Mullen Electric CO. — free Get an email when a new federal OSHA severe-injury report for Mullen Electric CO. is published. One employer, no account, unsubscribe in one click.
Establishment
MULLEN ELECTRIC CO.
Site address
1670 KOHLER'S CROSSING
City
KYLE
State
TX
ZIP
78640
Mailing
251 BRITNI LOOP, KYLE, TX 78640
Inspection type
Federal Agency (M)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
1
Ownership type
A

4 citations on file for this inspection.

1910.26 C02 VII

Serious Gravity 1 1 instance 1 exposed
Issued
Feb 7, 2013
Abate by
Feb 8, 2013
Penalty
Initial $1,200 · Current $800 Reduced
29 CFR 1910.26(c)(2)(vii): Ladders having defects were not marked and taken out of service until repaired.  On or about September 04, 2012, an employee was using a Louisville, 40-foot extension ladder that was extended approximately 21 feet to repair the Lithonia ballast, enclosed Low Bay lamp with light bulb. The ladder was missing the rope to disengage the locking mechanism, exposing the employee to the hazard of being struck by the extended ladder.  Pursuant to 29 C.F.R. 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps that it is taking to ensure that ladders having defects are marked and taken out of service until repaired.
Recent events (2)
  • — I (S) $800
  • — Z (S) $1200

1910.333 C07

Serious Gravity 10 1 instance 1 exposed
Issued
Feb 7, 2013
Abate by
Feb 8, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.333(c)(7): Portable ladders shall have nonconductive side rails if they are used where the employee or the ladder could contact exposed energized parts.  On or about September 04, 2012, an employee was working from a 40-foot aluminum extension ladder extended to 21 feet, repairing a Lithonia ballast, enclosed Low Bay lamp with light bulb. The ladder was aluminum and was not equipped with non-conductive side rails, exposing the employee to an electrical shock hazard.  Pursuant to 29 C.F.R. 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps to ensure that portable ladders will have nonconductive side rails if they are used where the employee or the ladder can come into contact with energized electrical parts.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.333 A02

Serious Gravity 10 1 instance 1 exposed
Issued
Feb 7, 2013
Abate by
Feb 8, 2013
Penalty
Initial $2,800 · Current $2,000 Reduced
29 CFR 1910.333(a)(2): Where exposed live parts were not deenergized, other safety related work practices were not used to protect employees who could be exposed to the electrical hazards involved.  On or about September 04, 2012, an employee was working from a 40-foot, aluminum extension ladder that was extended to 21 feet, repairing a Lithonia ballast, enclosed Low Bay lamp with light bulb. The light switch was in the "on" position and the circuit was not de-energized, exposing the employee to an electrical shock hazard.  Pursuant to 29 C.F.R. 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps that it is taking to ensure that safety related work practices are used to protect employees who are exposed to the electrical hazards involved.
Recent events (2)
  • — I (S) $2000
  • — Z (S) $2800

1910.333 C02

Serious Gravity 10 1 instance 1 exposed
Issued
Feb 7, 2013
Abate by
Feb 8, 2013
Penalty
Initial $2,800 · Current $2,000 Reduced
29 CFR 1910.333(c)(2): The employer did not ensure that only qualified persons were working on energized circuits and that qualified persons were familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools.  On or about September 04, 2012, an unqualified employee was working from a 40-foot, aluminum extension ladder extended to 21 feet, repairing a Lithonia ballast, enclosed Low Bay lamp with light bulb. The employee was not qualified to work on the 480-Volt light that was energized, exposing the employee to an electrical shock hazard.  Pursuant to 29 C.F.R. 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps that it is taking to ensure that only qualified persons are working on energized circuits and that they are familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools.
Recent events (2)
  • — I (S) $2000
  • — Z (S) $2800

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 336143193.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.