Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: EARL INDUSTRIES

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of EARL INDUSTRIES in 2 HARPER AVE, PORTSMOUTH, VA 23707 (NAICS 336611). OSHA activity number 336199187.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Earl Industries — free Get an email when a new federal OSHA severe-injury report for Earl Industries is published. One employer, no account, unsubscribe in one click.
Establishment
EARL INDUSTRIES
Site address
2 HARPER AVE
City
PORTSMOUTH
State
VA
ZIP
23707
Mailing
2 HARPER AVE, PORTSMOUTH, VA 23707
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
336611
Employees
584
Ownership type
A

2 citations on file for this inspection.

1910.304 B03 II A

Serious Gravity 5 1 instance 2 exposed
Issued
Sep 28, 2012
Penalty
Initial $3,000 · Current $1,500 Reduced
29 CFR 1910.304(b)(3)(ii)(A):     All 125-volt, single-phase, 15-, 20-, and 30-ampere receptacle outlets that are not part of the permanent wiring of the building or structure and that are in use by personnel shall have ground-fault circuit-interrupter protection for personnel.  Note 1 to paragraph (b)(3)(ii)(A) of this section: A cord connector on an extension cord set is considered to be a receptacle outlet if the cord set is used for temporary electric power.  Note 2 to paragraph (b)(3)(ii)(A) of this section: Cord sets and devices incorporating the required ground-fault circuit-interrupter that are connected to the receptacle closest to the source of power are acceptable forms of protection.    a.) Sheet metal shop: On or about 09/06/12, ground-fault circuit-interrupter protection was not provided while employee used a portable grinder and pedestal fan plugged into the receptacle outlets on the Syncrowave 250 DX portable welding unit.
Recent events (2)
  • — I (S) $1500
  • — Z (S) $3000

1910.303 B02

Other-than-serious 1 instance 4 exposed
Issued
Sep 28, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2):     Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling.    a.) Admin Office: On or about 09/07/12, 4 metal duplex receptacles used to supply power to computers and other office equipment were not used in accordance with the listing and labeling in that the duplex receptacles were not mounted.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Earl Industries's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 336199187.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.