Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: CASCADES TISSUE GROUP PENNSYLVANIA LLC

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of CASCADES TISSUE GROUP PENNSYLVANIA LLC in 1 MAIN STREET, RANSOM, PA 18653 (NAICS 322121). OSHA activity number 336240791.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Cascades Tissue Group Pennsylvania LLC — free Get an email when a new federal OSHA severe-injury report for Cascades Tissue Group Pennsylvania LLC is published. One employer, no account, unsubscribe in one click.
Site address
1 MAIN STREET
City
RANSOM
State
PA
ZIP
18653
Mailing
1 MAIN STREET, RANSOM, PA 18653
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
322121
Employees
75
Ownership type
A

2 citations on file for this inspection.

1910.305 E01

Serious Gravity 5 2 instances 20 exposed
Issued
Jan 28, 2013
Abate by
Mar 2, 2013
Penalty
Initial $3,825 · Current $1,700 Reduced
29 CFR 1910.305(e)(1):     Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures:    a) Poly Plant Motor Control Center near stock chests, the electrical enclosures near the eastern wall were exposed to water from a leaking roof.  The enclosures were not approved for wet locations which created a fire and electrical shock hazard, September 11, 2012.    b) Paper Machine #4, electrical enclosures near the western wall by paper machine #4 were exposed to water from a leaking roof. The enclosures were not approved for wet locations which created a fire and electrical shock hazard, September 11, 2012.    "ABATEMENT CERTIFICATION REQUIRED"
Recent events (2)
  • — I (S) $1700
  • — Z (S) $3825

1910.303 B07 I

Serious Gravity 1 1 instance 10 exposed
Issued
Jan 28, 2013
Abate by
Mar 2, 2013
Penalty
Initial $2,295 · Current $2,295
29 CFR 1910.303(b)(7)(i):     Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment.    a) Poly Plant Motor Control Center near stock chests, a panel was missing from the top front face of one enclosure, thus exposing live parts, September 11, 2012.    "ABATEMENT CERTIFICATION REQUIRED"
Recent events (2)
  • — I (S) $2295
  • — Z (S) $2295

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 336240791.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.